conditions or performance requirements are provided, the equipment shall satisfy all stated requirements unless otherwise exempted by footnotes in the table. Equipment covered under the Federal Energy Policy Act of 1992 (EPACT) shall have no minimum efficiency requirements for operation at minimum capacity or other than standard rating conditions. Equipment used to provide service water-heating functions as part of a combination system shall satisfy all stated requirements for the appropriate space heating or cooling category.

Tables are as follows:

a. Table 6.8.1-1, “Electrically Operated Unitary Air Conditioners and Condensing Units—Minimum Effi ciency Requirements” b. Table 6.8.1-2, “Electrically Operated Air-Cooled Unitary Heat Pumps—Minimum Efficiency Require ments” c. Table 6.8.1-3, “Liquid-Chilling Packages—Minimum Efficiency Requirements” (See Section 6.4.1.2 for

liquid-cooled centrifugal liquid-chilling packages that are designed to operate at nonstandard conditions.) d. Table 6.8.1-4, “Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat

Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air Conditioner Heat Pumps—Minimum Efficiency Requirements” e. Table 6.8.1-5, “Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units,

Warm-Air Duct Furnaces, and Unit Heaters—Minimum Efficiency Requirements” f. Table 6.8.1-6, “Gas- and Oil-Fired Boilers—Minimum Efficiency Requirements” g. Table 6.8.1-7, “Performance Requirements for Heat-Rejection Equipment—Minimum Efficiency

Requirements” h. Table 6.8.1-8, “Electrically Operated Variable-Refrigerant-Flow Air Conditioners—Minimum Effi ciency Requirements” i. Table 6.8.1-9, “Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements j. Table 6.8.1-10, “Floor-Mounted Air Conditioners and Condensing Units Serving Computer Rooms— Minimum Efficiency Requirements” k. Table 6.8.1-11, “Commercial Refrigerators, Commercial Freezers, and Refrigeration—Minimum Effi ciency Requirements” l. Table 6.8.1-12, “Vapor-Compression-Based Indoor Pool Dehumidifiers—Minimum Efficiency Requirements” m. Table 6.8.1-13, “Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, with out Energy Recovery—Minimum Efficiency Requirements” n. Table 6.8.1-14, “Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, with

Energy Recovery—Minimum Efficiency Requirements” o. Table 6.8.1-15, “Electrically Operated Water-Source Heat Pumps—Minimum Efficiency Requirements” p. Table 6.8.1-16, “Heat Pump and Heat Recovery Water-Chilling Packages—Minimum Efficiency

Requirement” q. Table 6.8.1-17, “Ceiling-Mounted Computer-Room Air Conditioners—Minimum Efficiency Require ments” r. Table 6.8.1-18, “Walk-In Cooler and Freezer Display Door Efficiency Requirements” s. Table 6.8.1-19, “Walk-In Cooler and Freezer Nondisplay Door Efficiency Requirements” t. Table 6.8.1-20, “Walk-In Cooler and Freezer Refrigeration System Efficiency Requirements” u. Table 6.8.1-21, “Ceiling Fan Efficiency Requirements”

6.4.1.2 Minimum Equipment Efficiencies—Listed Equipment—Nonstandard Conditions 6.4.1.2.1 Liquid-Cooled Centrifugal Chilling Package Cooling Efficiency Adjustment. Liquidcooled centrifugal chiller packages not designed for cooling operation at AHRI Standard 550/590 test and rating conditions of 44.00°F leaving and 54.00°F entering chilled-liquid temperatures, and with 85.00°F entering and 94.30°F leaving condenser-liquid temperatures, shall have maximum full-load kW /ton (FL) and part-load cooling energy efficiency ( IPLV .IP) rating requirements, listed in Tables 6.8.1-3 and 6.8.1-16, adjusted using the following equations:

FL.IP adj = FL.IP/ Kadj PLV.IP adj = IPLV .IP/ Kadj

Kadj = A × B

where

74 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)