Table 6.5.6.1.2-1 Exhaust Air Energy Recovery Requirements for Ventilation SystemsOperating Less than 8000 Hours per Year

Climate Zone% Outdoor Air at Full Design Airflow RateCol3Col4Col5Col6Col7Col8Col9
Climate Zone10% and
** <20%**
20% and
** <30%**
30% and
<40%
40% and
<50%
50% and
<60%
60% and
<70%
70% and
<80%
80%
Climate ZoneDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfm
3B, 3C, 4B,
4C, 5B
NRNRNRNRNRNRNRNR
0B, 1B, 2B,5CNRNRNRNR26,00012,00050004000
6B28,00026,50011,00055004500350025001500
0A, 1A, 2A,
3A, 4A, 5A,
6A
26,00016,00055004500350020001000120
7,8450040002500100014012010080

NR—Not required

Table 6.5.6.1.2-2 Exhaust Air Energy Recovery Requirements for Ventilation SystemsOperating Greater than or Equal to 8000 Hours per Year

Climate Zone% Outdoor Air at Full Design Airflow RateCol3Col4Col5Col6Col7Col8Col9
Climate Zone10% and
<20%
20% and
<30%
30% and
<40%
40% and
<50%
50% and
<60%
60% and
<70%
70% and
< 80%
80%
Climate ZoneDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfm
3CNRNRNRNRNRNRNRNR
0B, 1B, 2B,
3B, 4C, 5C
NR19,50090005000400030001500120
0A, 1A, 2A,
3A, 4B, 5B
25002000100050014012010080
4A, 5A, 6A,
6B, 7, 8
2001301008070605040

NR—Not required

b. not allowed by ASHRAE/ASHE Standard 170 for use in energy recovery systems with leak age potential, or c. of Class 4 as defined in ASHRAE Standard 62.1. 7. Systems in Climate Zones 0 through 4 requiring dehumidification that employ series energy recovery and have a minimum SERR of 0.40. 8. Systems expected to operate less than 20 hours per week at the outdoor air percentage covered by Table 6.5.6.1.2-1. 9. Indoor pool dehumidifiers meeting Section 6.5.6.4.

6.5.6.1.2.1 Minimum Enthalpy Recovery Ratio. Energy recovery systems required by this section shall result in an enthalpy recovery ratio of at least 50% at the cooling design condition.

At the heating design condition, energy recovery performance shall be as follows:

a. Where active humidification is provided to spaces served by the system, energy recovery systems shall

result in an enthalpy recovery ratio of at least 50%. b. Where active humidification is not provided to spaces served by the system, energy recovery systems

shall result in a sensible energy recovery ratio of at least 50%.

The energy recovery system shall provide the required enthalpy recovery ratio or sensible energy recov- ery ratio at both heating and cooling design conditions unless one mode is not required for the climate zone by the exception to Section 6.5.6.1.2.