Table 6.6.2.2 Mechanical Performance Factors (MPF)

Building TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Office
(small and
medium)a
0.720.710.700.700.680.650.710.660.620.690.640.650.720.660.650.740.700.750.77
Office (large)a0.830.830.840.840.790.820.720.840.780.690.800.670.720.750.670.730.730.710.70
Retail0.600.570.500.550.460.460.430.460.380.400.450.480.410.500.470.440.390.400.36
Hotel/motel0.620.620.630.630.620.680.610.710.730.590.660.650.550.590.680.510.540.470.40
Multifamily/
dormitory
0.640.630.670.630.650.640.590.680.540.590.570.520.580.530.480.570.530.550.52
School/education0.820.810.800.790.750.720.710.720.680.670.710.650.720.680.600.750.690.720.68

a. Office sizes defined in Section L1.1.1.1.

a. All HVAC systems in the building that meet the criteria in Section L1.1.1 shall comply with Section

6.6.2.2. b. All other HVAC systems shall comply with one of the following:

  1. HVAC systems shall comply with the applicable requirements in Section 6.5.
  2. HVAC systems that only serve the heating, cooling, or ventilating needs of a computer room with IT equipment load greater than 10 kW shall be permitted to comply with ANSI/ASHRAE Standard 90.4, Energy Standard for Data Centers . 6.6.2.2 Criteria. HVAC systems in new buildings, additions, or alterations shall comply with the requirements in Section L2, “Mechanical System Performance Rating Method.” The proposed design total system performance ratio ( TSPRp ) of the HVAC systems using this method shall be greater than or equal to the total system performance ratio of the TSPR reference building design ( TSPRr ) divided by the mechanical performance factor (MPF) when calculated in accordance with the following:

TSPRp - TSPRr /MPF

where TSPR p = proposed TSPR calculated in accordance with Normative Appendix L TSPR r = reference TSPR calculated in accordance with Normative Appendix L MPF = mechanical performance factor from Table 6.6.2.2 based on climate zone and building use type

Where a building has multiple building use types, MPF shall be area weighted as follows:

MPF = ( A 1 × MPF1 + A 2 × MPF2 + … + An × MPF n )/( A 1 + A 2 + … + An )

where MPF1, MPF2, …, MPF n = mechanical performance factors from Table 6.6.2.2 based on climate zone and building use types 1 through n A 1, A 2, …, An = gross conditioned floor areas for building use types 1 through n Informative Note: The Mechanical System Performance Rating Method is a simplified performance trade-off approach for HVAC systems that does not require using the whole- building trade-off approaches in Section 12 or Normative Appendix G. HVAC systems that are allowed to use this approach will not need to comply with all of the prescriptive requirements in Section 6.5. For example, an HVAC system without a required outdoor air economizer can show compliance with Section 6 by demonstrating improved cooling efficiency or reduced fan energy use compared to a reference HVAC system that meets all prescriptive requirements, including outdoor air economizers . This approach does not allow HVAC system efficiency trade-offs with building envelope, plug loads , or lighting systems .

6.7 Submittals 6.7.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.

6.7.2 Permit Application Documentation (Not Used) 6.7.3 Completion Requirements