Table 6.8.1-1 Electrically Operated Unitary Air Conditioners and Condensing Units—Minimum Efficiency Requirements (Continued)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedurea
Air conditioners,
air cooled (continued)
240,000 Btu/h and
<760,000 Btu/h
Electric resistance
(or none)
Split_system_ and
single package
10.0_EER_
11.6_IEER_
before 1/1/2023
13.2_IEER_
after 1/1/2023
AHRI 340/360
Air conditioners,
air cooled (continued)
240,000 Btu/h and
<760,000 Btu/h
All otherAll other9.8_EER_
11.4_IEER_
before 1/1/2023
13.0_IEER_
after 1/1/2023
9.8_EER_
11.4_IEER_
before 1/1/2023
13.0_IEER_
after 1/1/2023
Air conditioners,
air cooled (continued)
760,000 Btu/hElectric resistance
(or none)
Electric resistance
(or none)
9.7_EER_
11.2_IEER_
before 1/1/2023
12.5_IEER_
after 1/1/2023
9.7_EER_
11.2_IEER_
before 1/1/2023
12.5_IEER_
after 1/1/2023
Air conditioners,
air cooled (continued)
760,000 Btu/hAll otherAll other9.5_EER_
11.0_IEER_
before 1/1/2023
12.3_IEER_
after 1/1/2023
9.5_EER_
11.0_IEER_
before 1/1/2023
12.3_IEER_
after 1/1/2023
Air conditioners,
water cooled
<65,000 Btu/hAllSplit_system_ and
single package
12.1_EER_
12.3_IEER_
AHRI 210/240
Air conditioners,
water cooled
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.1_EER_
13.9_IEER_
AHRI 340/360
Air conditioners,
water cooled
65,000 Btu/h and
<135,000 Btu/h
All otherAll other11.9_EER_
13.7_IEER_
11.9_EER_
13.7_IEER_
Air conditioners,
water cooled
135,000 Btu/h and
<240,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.5_EER_
13.9_IEER_
12.5_EER_
13.9_IEER_
Air conditioners,
water cooled
135,000 Btu/h and
<240,000 Btu/h
All otherAll other12.3_EER_
13.7_IEER_
12.3_EER_
13.7_IEER_
Air conditioners,
water cooled
240,000 Btu/h and
<760,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.4_EER_
13.6_IEER_
12.4_EER_
13.6_IEER_
Air conditioners,
water cooled
240,000 Btu/h and
<760,000 Btu/h
All otherAll other12.2_EER_
13.4_IEER_
12.2_EER_
13.4_IEER_
Air conditioners,
water cooled
760,000 Btu/hElectric resistance
(or none)
Electric resistance
(or none)
12.2_EER_
13.5_IEER_
12.2_EER_
13.5_IEER_
Air conditioners,
water cooled
760,000 Btu/hAll otherAll other12.0_EER_
13.3_IEER_
12.0_EER_
13.3_IEER_

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Single-phase, U.S. air-cooled air conditioners <65,000 Btu/h are regulated as consumer products by the U.S. Code of Federal Regulations 10 CFR 430. SEER and SEER2 values

for single-phase products are set by the U.S. Department of Energy. Informative Note: See Informative Appendix F for the U.S. Department of Energy minimum efficiency requirements of single-phase air conditioners for U.S. applications.