Table 6.8.1-2 Electrically Operated Air-Cooled Unitary Heat Pumps—Minimum Efficiency Requirements (Continued)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedurea
Air cooled
(heating mode)
<65,000 Btu/h
(cooling capacity)
Split_system_, three
phase and
applications outside
U.S. single phase b
8.2_HSPF_
before 1/1/2023
7.5_HSPF2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Air cooled
(heating mode)
<65,000 Btu/h
(cooling capacity)
Single package, three
phase and
applications outside
U.S. single phase b
8.0_HSPF_
before 1/1/2023
6.7_HSPF2_
after 1/1/2023
8.0_HSPF_
before 1/1/2023
6.7_HSPF2_
after 1/1/2023
Space constrained,
air cooled
(heating mode)
30,000 Btu/h
(cooling capacity)
Split_system_, three
phase and
applications outside
U.S. single phase b
7.4_HSPF_
before 1/1/2023
6.3_HSPF2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Space constrained,
air cooled
(heating mode)
30,000 Btu/h
(cooling capacity)
Single package, three
phase and
applications outside
U.S. single phase b
7.4_HSPF_
before 1/1/2023
6.3_HSPF2_
after 1/1/2023
7.4_HSPF_
before 1/1/2023
6.3_HSPF2_
after 1/1/2023
Small duct high
velocity, air cooled
(heating mode)
<65,000 Btu/hSplit_system_, three
phase and
applications outside
U.S. single phase b
7.2_HSPF_
before 1/1/2023
6.1_HSPF2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Air cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
47°F db/43°F wb
outdoor air
3.30_COPH_
before 1/1/2023
3.40_COPH_
after 1/1/2023
AHRI 340/360
Air cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.25_COPH_2.25_COPH_
Air cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
and <240,000 Btu/h
135,000 Btu/h
(cooling capacity)
and <240,000 Btu/h
47°F db/43°F wb
outdoor air
3.20_COPH_
before 1/1/2023
3.30_COPH_
after 1/1/2023
3.20_COPH_
before 1/1/2023
3.30_COPH_
after 1/1/2023
Air cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
and <240,000 Btu/h
135,000 Btu/h
(cooling capacity)
and <240,000 Btu/h
17°F db/15°F wb
outdoor air
2.05_COPH_2.05_COPH_
Air cooled
(heating mode)
240,000 Btu/h
(cooling capacity)
240,000 Btu/h
(cooling capacity)
47°F db/43°F wb
outdoor air
3.20_COPH_3.20_COPH_
Air cooled
(heating mode)
240,000 Btu/h
(cooling capacity)
240,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.05_COPH_2.05_COPH_

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Single-phase, U.S. air-cooled heat pumps <65,000 Btu/h are regulated as consumer products by the U.S. Code of Federal Regulations 10 CFR 430. SEER, SEER2, and HSPF values

for single-phase products are set by the U.S. Department of Energy. Informative Note: See Informative Appendix F for the U.S. Department of Energy minimum.

112 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)