ASHRAE-90.1-2022- - Page 115

Extracted Content

Table 6.8.1-3 Liquid-Chilling Packages—Minimum Efficiency Requirements [a,b,e]

Equipment TypeSize CategoryUnitsPath APath BTest Procedurec
Air-cooled<150 tonsEER(Btu/Wh)10.100 FL9.700 FLAHRI 550/590
Air-cooled<150 tonsEER(Btu/Wh)13.700_ IPLV_.IP15.800_IPLV_.IP15.800_IPLV_.IP
Air-cooled150 tons150 tons10.100 FL9.700 FL9.700 FL
Air-cooled150 tons150 tons14.000_IPLV_.IP16.100_IPLV_.IP16.100_IPLV_.IP
Air-cooled without
condenser, electrically
operated
All capacitiesEER(Btu/Wh)Air-cooled without condenser must be rated
with matching condensers and comply with
air-cooled chiller_efficiency_ requirements.
Air-cooled without condenser must be rated
with matching condensers and comply with
air-cooled chiller_efficiency_ requirements.
AHRI 550/590
Liquid-cooled,
electrically operated
positive displacement
<75 tonskW/ton0.750 FL0.780 FLAHRI 550/590
Liquid-cooled,
electrically operated
positive displacement
<75 tonskW/ton0.600_IPLV_.IP0.500_IPLV_.IP0.500_IPLV_.IP
Liquid-cooled,
electrically operated
positive displacement
75 tons and
<150 tons
75 tons and
<150 tons
0.720 FL0.750 FL0.750 FL
Liquid-cooled,
electrically operated
positive displacement
75 tons and
<150 tons
75 tons and
<150 tons
0.560_IPLV_.IP0.490_IPLV_.IP0.490_IPLV_.IP
Liquid-cooled,
electrically operated
positive displacement
150 tons and
<300 tons
150 tons and
<300 tons
0.660 FL0.680 FL0.680 FL
Liquid-cooled,
electrically operated
positive displacement
150 tons and
<300 tons
150 tons and
<300 tons
0.540_IPLV_.IP0.440_IPLV_.IP0.440_IPLV_.IP
Liquid-cooled,
electrically operated
positive displacement
300 tons and
<600 tons
300 tons and
<600 tons
0.610 FL0.625 FL0.625 FL
Liquid-cooled,
electrically operated
positive displacement
300 tons and
<600 tons
300 tons and
<600 tons
0.520_IPLV_.IP0.410_IPLV_.IP0.410_IPLV_.IP
Liquid-cooled,
electrically operated
positive displacement
600 tons600 tons0.560 FL0.585 FL0.585 FL
Liquid-cooled,
electrically operated
positive displacement
600 tons600 tons0.500_IPLV_.IP0.380_IPLV_.IP0.380_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
<150 tonskW/ton0.610 FL0.695 FLAHRI 550/590
Liquid-cooled,
electrically operated
centrifugal
<150 tonskW/ton0.550_IPLV_.IP0.440_IPLV_.IP0.440_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
150 tons and
<300 tons
150 tons and
<300 tons
0.610 FL0.635 FL0.635 FL
Liquid-cooled,
electrically operated
centrifugal
150 tons and
<300 tons
150 tons and
<300 tons
0.550_IPLV_.IP0.400_IPLV_.IP0.400_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
300 tons and
<400 tons
300 tons and
<400 tons
0.560 FL0.595 FL0.595 FL
Liquid-cooled,
electrically operated
centrifugal
300 tons and
<400 tons
300 tons and
<400 tons
0.520_IPLV_.IP0.390_IPLV_.IP0.390_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
400 tons and
<600 tons
400 tons and
<600 tons
0.560 FL0.585 FL0.585 FL
Liquid-cooled,
electrically operated
centrifugal
400 tons and
<600 tons
400 tons and
<600 tons
0.500_IPLV_.IP0.380_IPLV_.IP0.380_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
600 tons600 tons0.560 FL0.585 FL0.585 FL
Liquid-cooled,
electrically operated
centrifugal
600 tons600 tons0.500_IPLV_.IP0.380_IPLV_.IP0.380_IPLV_.IP
Air-cooled absorption,
single effect
All capacitiesCOP (W/W)0.600 FLNAdAHRI 560
Liquid-cooled
absorption,
single effect
All capacitiesCOP (W/W)0.700 FLNAdAHRI 560
Absorption double
effect, indirect fired
All capacitiesCOP (W/W)1.000 FLNAdAHRI 560
Absorption double
effect, indirect fired
All capacitiesCOP (W/W)1.050_IPLV_.IP1.050_IPLV_.IP1.050_IPLV_.IP
Absorption double
effect,
direct fired
All capacitiesCOP (W/W)1.000 FLNAdAHRI 560
Absorption double
effect,
direct fired
All capacitiesCOP (W/W)1.000_IPLV_1.000_IPLV_1.000_IPLV_

a. The requirements for centrifugal chilling packages shall be adjusted for nonstandard rating conditions per Section 6.4.1.2.1 and are only applicable for the range of conditions listed

there. The requirements for air-cooled, liquid-cooled positive displacement and absorption chilling packages are at standard rating conditions defined in the reference test procedure. b. Both the full-load and IPLV .IP requirements must be met or exceeded to comply with this standard. When there is a Path B, compliance can be with either Path A or Path B for

any application. c. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. d. NA means the requirements are not applicable for Path B, and only Path A can be used for compliance. e. FL is the full-load performance requirements, and IPLV .IP is for the part-load performance requirements. f. Electrically operated chilling packages employing a freeze-protection liquid in accordance with Section 6.4.1.2.2 shall be tested or rated with water for the purpose of compliance

with the requirements of this table.