Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single- Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air- Conditioner Heat Pumps—Minimum Efficiency Requirements

Equipment TypeSize
Category (Input)
Subcategory or
Rating Condition
Minimum EfficiencydTest Procedurea
PTAC (cooling mode)
standard size
<7000 Btu/h95°F db/75°F wb
_outdoor air_c
11.9_EER_
AHRI 310/380
PTAC (cooling mode)
standard size
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
14.0 – (0.300 × Cap/1000)_EER_e14.0 – (0.300 × Cap/1000)_EER_e
PTAC (cooling mode)
standard size
>15,000 Btu/h>15,000 Btu/h9.5_EER_9.5_EER_
PTAC (cooling mode)
nonstandard sizeb
<7000 Btu/h95°F db/75°F wb
_outdoor air_c
9.4_EER_
AHRI 310/380
PTAC (cooling mode)
nonstandard sizeb
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
10.9 – (0.213 × Cap/1000)_EER_e10.9 – (0.213 × Cap/1000)_EER_e
PTAC (cooling mode)
nonstandard sizeb
>15,000 Btu/h>15,000 Btu/h7.7_EER_7.7_EER_
PTHP (cooling mode)
standard size
<7000 Btu/h95°F db/75°F wb
_outdoor air_c
11.9_EER_
AHRI 310/380
PTHP (cooling mode)
standard size
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
14.0 – (0.300 × Cap/1000)_EER_e14.0 – (0.300 × Cap/1000)_EER_e
PTHP (cooling mode)
standard size
>15,000 Btu/h>15,000 Btu/h9.5_EER_9.5_EER_
PTHP (cooling mode)
nonstandard sizeb
<7000 Btu/h95°F db/75°F wb
_outdoor air_c
9.3_EER_
AHRI 310/380
PTHP (cooling mode)
nonstandard sizeb
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
10.8 – (0.213 × Cap/1000)_EER_e10.8 – (0.213 × Cap/1000)_EER_e
PTHP (cooling mode)
nonstandard sizeb
>15,000 Btu/h>15,000 Btu/h7.6_EER_7.6_EER_
PTHP (heating mode)
standard size
<7000 Btu/h47°F db/43°F wb
outdoor air
3.3_COPH_
AHRI 310/380
PTHP (heating mode)
standard size
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
3.7 – (0.052 × Cap/1000)COPH
e
3.7 – (0.052 × Cap/1000)COPH
e
PTHP (heating mode)
standard size
>15,000 Btu/h>15,000 Btu/h2.90_COPH_2.90_COPH_
PTHP (heating mode)
nonstandard sizeb
<7000 Btu/h47°F db/43°F wb
outdoor air
2.7_COPH_
AHRI 310/380
PTHP (heating mode)
nonstandard sizeb
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
2.9 – (0.026 × Cap/1000)COPH
e
2.9 – (0.026 × Cap/1000)COPH
e
PTHP (heating mode)
nonstandard sizeb
>15,000 Btu/h>15,000 Btu/h2.5_COPH_2.5_COPH_
SPVAC (cooling mode)
single and three phase
<65,000 Btu/h95°F db/75°F wb
_outdoor air_c
11.0_EER_AHRI 390
SPVAC (cooling mode)
single and three phase
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
10.0_EER_10.0_EER_
SPVAC (cooling mode)
single and three phase
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
10.0_EER_10.0_EER_
SPVHP (cooling mode)<65,000 Btu/h95°F db/75°F wb
_outdoor air_c
11.0_EER_AHRI 390
SPVHP (cooling mode)65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
10.0_EER_
SPVHP (cooling mode)135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
10.0_EER_
SPVHP (heating mode)<65,000 Btu/h47°F db/43°F wb
outdoor air
3.3_COPH_AHRI 390
SPVHP (heating mode)65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
3.0_COPH_3.0_COPH_
SPVHP (heating mode)135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
3.0_COPH_3.0_COPH_

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Nonstandard size units must be factory labeled as follows: “MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW STANDARD PROJECTS.” Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 in. high or less than 42 in. wide and having a cross-sectional area less than 670 in. [2] . c. The cooling-mode wet bulb temperature requirement only applies for units that reject condensate to the condenser coil. d. Room air conditioners are regulated as consumer products by 10 CFR 430. For U.S. applications of room air conditioners, refer to Informative Appendix F, Table F-3, for the

U.S. DOE minimum efficiency requirements for U.S. applications. e. “Cap” in EER and COPH equations for PTAC s and PTHP s means cooling capacity in Btu/h at 95°F outdoor dry-bulb temperature.

114 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)