Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single- Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air- Conditioner Heat Pumps—Minimum Efficiency Requirements (Continued)

Equipment TypeSize
Category (Input)
Subcategory or
Rating Condition
Minimum EfficiencydTest Procedurea
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
<6000 Btu/h11.0_CEER_ANSI/AHAM
RAC-1
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
6000 Btu/h and
<8000 Btu/h
6000 Btu/h and
<8000 Btu/h
11.0_CEER_11.0_CEER_
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
8000 Btu/h and
<14,000 Btu/h
8000 Btu/h and
<14,000 Btu/h
10.9_CEER_10.9_CEER_
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
14,000 Btu/h and
<20,000 Btu/h
14,000 Btu/h and
<20,000 Btu/h
10.7_CEER_10.7_CEER_
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
20,000 Btu/h and
<28,000 Btu/h
20,000 Btu/h and
<28,000 Btu/h
9.4_CEER_9.4_CEER_
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
28,000 Btu/h28,000 Btu/h9.0_CEER_9.0_CEER_
Room air conditioners
without louvered sides
<6000 Btu/h<6000 Btu/h10.0_CEER_ANSI/AHAM
RAC-1
Room air conditioners
without louvered sides
6000 Btu/h and
<8000 Btu/h
6000 Btu/h and
<8000 Btu/h
10.0_CEER_10.0_CEER_
Room air conditioners
without louvered sides
8000 Btu/h and
<11,000 Btu/h
8000 Btu/h and
<11,000 Btu/h
9.6_CEER_9.6_CEER_
Room air conditioners
without louvered sides
11,000 Btu/h and
<14,000 Btu/h
11,000 Btu/h and
<14,000 Btu/h
9.5_CEER_9.5_CEER_
Room air conditioners
without louvered sides
14,000 Btu/h and
<20,000 Btu/h
14,000 Btu/h and
<20,000 Btu/h
9.3_CEER_9.3_CEER_
Room air conditioners
without louvered sides
20,000 Btu/h20,000 Btu/h9.4_CEER_9.4_CEER_
Room air conditioners with reverse
cycle, with louvered sides for
applications outside U.S. d
<20,000 Btu/h<20,000 Btu/h9.8_CEER_ANSI/AHAM
RAC-1
Room air conditioners with reverse
cycle, with louvered sides for
applications outside U.S. d
20,000 Btu/h20,000 Btu/h9.3_CEER_9.3_CEER_
Room air conditioners with reverse
cycle without louvered sides for
applications outside U.S. d
<14,000 Btu/h<14,000 Btu/h9.3_CEER_ANSI/AHAM
RAC-1
Room air conditioners with reverse
cycle without louvered sides for
applications outside U.S. d
14,000 Btu/h14,000 Btu/h8.7_CEER_8.7_CEER_
Room air conditioners, casement only
for applications outside U.S. d
AllAll9.5_CEER_ANSI/AHAM
RAC-1
Room air conditioners, casement
slider for applications outside U.S. d
AllAll10.4_CEER_ANSI/AHAM
RAC-1

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Nonstandard size units must be factory labeled as follows: “MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW STANDARD PROJECTS.” Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 in. high or less than 42 in. wide and having a cross-sectional area less than 670 in. [2] . c. The cooling-mode wet bulb temperature requirement only applies for units that reject condensate to the condenser coil. d. Room air conditioners are regulated as consumer products by 10 CFR 430. For U.S. applications of room air conditioners, refer to Informative Appendix F, Table F-3, for the

U.S. DOE minimum efficiency requirements for U.S. applications. e. “Cap” in EER and COPH equations for PTAC s and PTHP s means cooling capacity in Btu/h at 95°F outdoor dry-bulb temperature.