Table 6.8.1-5 Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct

Furnaces, and Unit Heaters—Minimum Efficiency Requirements (Continued)Col2Col3Col4Col5Col6Col7Col8Col9
Equipment TypeEquipment TypeEquipment TypeEquipment TypeEquipment TypeEquipment TypeEquipment TypeMinimum
Efficiency b

Test
Procedure a
DescriptionFuelElectric
Power Phase
Application
Location
Heating
Capacity
(input),
Btu/h b
Combo-Unit
Cooling
Capacity,
Btu/h
SubtypeSubtypeSubtype
Warm-air
furnace
Oil3All<225,000AllNonweatherized83%AFUEAppendix N g
Warm-air
furnace
Oil3All<225,000AllWeatherized78%AFUE or
80%Et
d
Appendix N g
Warm-air
furnace
Oil3All<225,000AllWeatherized78%AFUE or
80%Et
d
Section 42
UL 727
Warm-air
furnace
OilAllAll≥225,000AllAll
81%Et
d
before 1/1/2023
82%Et
d
after 1/1/2023
Section 42
UL 727
Warm-air
furnace
Electric1Inside U.S.<225,000<65,000See Informative Appendix F, Table F-4 f
See Informative Appendix F, Table F-4 f
See Informative Appendix F, Table F-4 f
Warm-air
furnace
Electric1Inside U.S.<225,000≥65,000All96%AFUEAppendix N g
Warm-air
furnace
Electric1Outside U.S.<225,000AllAll96%AFUEAppendix N g
Warm-air
furnace
Electric3All<225,000AllAll96%AFUE
Appendix N g
Warm-air
duct furnaces
GasAllAllAllAllAll80%Ec
d
ANSI Z83.8
Warm-air
unit heaters
GasAllAllAllAllAll80%Ec
d,e
ANSI Z83.8
Warm-air
unit heaters
OilAllAllAllAllAll80%Ec
d,e
Section 40
UL 731

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. For this table, the following applies:

  • Appendix N = 10 CFR 430 Appendix N

  • ANSI Z21.47 = Section 2.39, Thermal Efficiency, ANSI Z21.47

  • ANSI Z83.3 = Section 2.10, Efficiency, ANSI Z83.3

  • UL 727 = Section 42, Combustion, UL 727

  • UL 731 = Section 40, Combustion, UL 731 b. Compliance of multiple firing rate units shall be at the maximum firing rate. c. Et = thermal efficiency . Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75% of the input rating, and have either

power venting or a flue damper . A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space . d. Ec = combustion efficiency (100% less flue losses). See test procedure for detailed discussion. e. Units must also include an interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper . f. Includes combination units with cooling capacity <65,000 Btu/h. For U.S. applications of federally covered <225,000 Btu/h products, see Informative Appendix F, Table F-4. g. 10 CFR 430 is limited to-single phase equipment that is not contained within the same cabinet with a central air conditioner whose rated cooling capacity is above 65,000 Btu/

h but for the test and rating procedures are not impacted for three-phase and can be used for AFUE ratings for ASHRAE/IES Standard 90.1 three-phase products and single-phase products with a cooling capacity greater than 65,000 Btu/h.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 117