ASHRAE-90.1-2022- - Page 120

Extracted Content

Table 6.8.1-6 Gas- and Oil-Fired Boilers—Minimum Efficiency Requirements

Equipment Type aSubcategory or
Rating Condition
Size Category
(Input)
Minimum
Efficiency i
Efficiency as of
3/2/2022
Test Procedure
Boilers,
hot water
Gas fired h<300,000 Btu/h f,g for
applications outside
U.S. i
82%AFUE82%AFUE10 CFR 430
Appendix N
Boilers,
hot water
Gas fired h300,000 Btu/h and
2,500,000 Btu/hd
80%Et
c
80%Et
c
10 CFR 431.86
Boilers,
hot water
Gas fired h>2,500,000 Btu/h d82%Ec
b
82%Ec
b
82%Ec
b
Boilers,
hot water
Oil fired e<300,000 Btu/h f,g for
applications outside
U.S. i
84%AFUE84%AFUE10 CFR 430
Appendix N
Boilers,
hot water
Oil fired e300,000 Btu/h and
2,500,000 Btu/hd
82%Et
c
82%Et
c
10 CFR 431.86
Boilers,
hot water
Oil fired e>2,500,000 Btu/h d84%Ec
b
84%Ec
b
84%Ec
b
Boilers,
steam
Gas fired<300,000 Btu/hf for
applications outside
U.S. i
80%AFUE80%AFUE10 CFR 430
Appendix N
Boilers,
steam
Gas fired—
all, except
natural draft
300,000 Btu/h and
2,500,000 Btu/hd
79%Et
c
79%Et
c
10 CFR 431.86
Boilers,
steam
Gas fired—
all, except
natural draft
>2,500,000 Btu/h d79%Et
c
79%Et
c
79%Et
c
Boilers,
steam
Gas fired—
natural draft
300,000 Btu/h and
2,500,000 Btu/hd
77%Et
c
79%Et
c
79%Et
c
Boilers,
steam
Gas fired—
natural draft
>2,500,000 Btu/h d77%Et
c
79%Et
c
79%Et
c
Boilers,
steam
Oil fired e<300,000 Btu/h f for
applications outside
U.S. i
82%AFUE82%AFUE10 CFR 430
Appendix N
Boilers,
steam
Oil fired e300,000 Btu/h and
2,500,000 Btu/hd
81%Et
c
81%Et
c
10 CFR 431.86
Boilers,
steam
Oil fired e>2,500,000 Btu/h d81%Et
c
81%Et
c
81%Et
c

a. These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers . Minimum efficiency requirements for

boilers cover all capacities of packaged boilers . b. Ec = combustion efficiency (100% less flue losses). See reference document for detailed information. c. Et = thermal efficiency . See reference document for detailed information. d. Maximum capacity—minimum and maximum ratings as provided for and allowed by the unit’s controls. e. Includes oil-fired (residual). f. Boilers shall not be equipped with a constant burning pilot light. g. A boiler not equipped with a tankless domestic water-heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental

change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied. h. For new construction, refer to Section 6.4.1.1 for additional system compliance requirements. i. See Informative Appendix F, Table F-4, for U.S. minimum efficiencies for residential products covered by U.S. DOE requirements for U.S. applications.

118 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)