ASHRAE-90.1-2022- - Page 121

Extracted Content

Table 6.8.1-7 Performance Requirements for Heat Rejection Equipment—Minimum Efficiency Requirements

Equipment TypeTotal System
Heat-Rejection Capacity
at Rated Conditions
Subcategory or
Rating Condition h
Performance
Required a,b,c,f,g
Test Procedure d,e
Propeller or axial fan
open-circuit cooling
towers
All95°F entering water
85°F leaving water
75°F entering wb
40.2 gpm/hpCTI ATC-105 and
CTI STD-201 RS
Centrifugal fan
open-circuit cooling
towers
All95°F entering water
85°F leaving water
75°F entering wb
20.0 gpm/hpCTI ATC-105 and
CTI STD-201 RS
Propeller or axial fan
closed-circuit cooling
towers
All102°F entering water
90°F leaving water
75°F entering wb
16.1 gpm/hpCTI ATC-105S and
CTI STD-201 RS
Centrifugal fan closed-
circuit cooling towers
All102°F entering water
90°F leaving water
75°F entering wb
7.0 gpm/hpCTI ATC-105S and
CTI STD-201 RS
Propeller or axial fan
dry coolers
(air-cooled fluid coolers)
All115°F entering water
105°F leaving water
95°F entering db
4.5 gpm/hpCTI ATC-105DS
Propeller or axial fan
evaporative condensers
AllR-448A test fluid
165°F entering gas temperature
105°F condensing temperature
75°F entering wb
160,000 Btu/h·hpCTI ATC-106
Propeller or axial fan
evaporative condensers
AllAmmonia test fluid
140°F entering gas temperature
96.3°F condensing temperature
75°F entering wb
134,000 Btu/h·hpCTI ATC-106
Centrifugal fan
evaporative condensers
AllR-448A test fluid
165°F entering gas temperature
105°F condensing temperature
75°F entering wb
137,000 Btu/h·hpCTI ATC-106
Centrifugal fan
evaporative condensers
AllAmmonia test fluid
140°F entering gas temperature
96.3°F condensing temperature
75°F entering wb
110,000 Btu/h·hpCTI ATC-106
Air-cooled condensersAll125°F condensing temperature
190°F entering gas temperature
15°F subcooling
95°F entering db
176,000 Btu/h·hpAHRI 460

a. For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the thermal rating condition listed in Table 6.8.1-7 divided

by the fan motor nameplate power. b. For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the thermal rating condition listed in Table 6.8.1-7

divided by the sum of the fan motor nameplate power and the integral spray pump motor nameplate power. c. For purposes of this table, dry-cooler performance is defined as the process water flow rating of the unit at the thermal rating condition listed in Table 6.8.1-7 divided by the total

fan motor nameplate power of the unit, and air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the total fan motor nameplate power of the unit. d. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. e. The efficiencies and test procedures for both open- and closed-circuit cooling towers are not applicable to hybrid cooling towers that contain a combination of separate wet and

dry heat exchange sections. The certification requirements do not apply to field-erected cooling towers. f. All cooling towers shall comply with the minimum efficiency listed in the table for that specific type of tower with the capacity effect of any project-specific accessories and/or

options included in the capacity of the cooling tower. g. For purposes of this table, evaporative condenser performance is defined as the heat rejected at the specified rating condition in the table, divided by the sum of the fan motor name plate power and the integral spray pump nameplate power. h. Requirements for evaporative condensers are listed with ammonia (R-717) and R-448A as test fluids in the table. Evaporative condensers intended for use with halocarbon refrig erants other than R-448A must meet the minimum efficiency requirements listed above with R-448A as the test fluid. For ammonia, the condensing temperature is defined as the saturation temperature corresponding to the refrigerant pressure at the condenser entrance. For R-448A, which is a zeotropic refrigerant, the condensing temperature is defined as the arithmetic average of the dew point and the bubble point temperatures corresponding to the refrigerant pressure at the condenser entrance.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 119