Table 6.8.1-8 Electrically Operated Variable-Refrigerant-Flow Air Conditioners—Minimum Efficiency Requirements

Equipment TypeaSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
VRF air conditioners,
air cooled
<65,000 Btu/h
Three-phase for
applications in the U.S.
and single- and three-
phase for applications
outside the U.S.
AllVRF multisplit_system_13.0_SEER_
Before 1/1/23
SEER2 = 13.4
On or after 1/1/23
AHRI 1230-2014 with
Addendum 1
before 1/1/2023
AHRI 210/240-2023
on or after 1/1/2023
VRF air conditioners,
air cooled
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
VRF multisplit_ system_11.2_EER_
15.5_IEER_
Before 1/1/2024
10.5_EER_
15.5_IEER_
On or after 1/1/24
AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF air conditioners,
air cooled
135,000 Btu/h and
<240,000 Btu/h
Electric resistance
(or none)
VRF multisplit_system_11.0_EER_
14.9_IEER_
Before 1/1/2024
10.3_EER_
14.9_IEER_
On or after 1/1/24
11.0_EER_
14.9_IEER_
Before 1/1/2024
10.3_EER_
14.9_IEER_
On or after 1/1/24
VRF air conditioners,
air cooled
240,000 Btu/hElectric resistance
(or none)
VRF multisplit_system_10.0_EER_
13.9_IEER_
Before 1/1/2024
9.5_EER_
13.9_IEER_
On or after 1/1/24
10.0_EER_
13.9_IEER_
Before 1/1/2024
9.5_EER_
13.9_IEER_
On or after 1/1/24

a. VRF outdoor units can be combined with innumerable indoor unit combinations, which will vary by application, building type, building size, operating conditions, and comfort

level goals. Selection of indoor units tested during the test is considered to be representative of commonly sold applications and is detailed in AHRI 1230. Informative Note: For single-phase VRF air conditioners, air-cooled systems less than 65,000 Btu/h see Informative Appendix F, Table F-1 for the U.S. Department of Energy mini mum.

120 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)