Table 6.8.1-9 Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
VRF air cooled
(cooling mode)
<65,000 Btu/h
Three-phase for
applications in the U.S.
and single- and three-
phase for applications
outside the U.S.
AllVRF multisplit_system_13.0_SEER_
Before 1/1/2023
SEER2 = 13.4
On or after 1/1/2023
AHRI 1230-2014 with
Addendum 1
before 1/1/2023
AHRI 210/240-2023
on or after 1/1/2023
VRF air cooled
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
11.0_EER_
14.6_IEER_
Before 1/1/2024
10.3_EER_
14.6_IEER_
On or after 1/1/24
AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF air cooled
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
VRF multisplit_system_
with heat recovery
10.8_EER_
14.4_IEER_
Before 1/1/2024
10.1_EER_
14.4_IEER_
On or after 1/1/24
10.8_EER_
14.4_IEER_
Before 1/1/2024
10.1_EER_
14.4_IEER_
On or after 1/1/24
VRF air cooled
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
VRF multisplit_system_10.6_EER_
13.9_IEER_
Before 1/1/2024
9.9_EER_
13.9_IEER_
On or after 1/1/24
10.6_EER_
13.9_IEER_
Before 1/1/2024
9.9_EER_
13.9_IEER_
On or after 1/1/24
VRF air cooled
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
VRF multisplit_system_
with heat recovery
10.4_EER_
13.7_IEER_
Before 1/1/2024
9.7_EER_
13.7_IEER_
On or after 1/1/24
10.4_EER_
13.7_IEER_
Before 1/1/2024
9.7_EER_
13.7_IEER_
On or after 1/1/24
VRF air cooled
(cooling mode)
240,000 Btu/h240,000 Btu/hVRF multisplit_system_9.5_EER_
12.7_IEER_
Before 1/1/2024
9.1_EER_
12.7_IEER_
On or after 1/1/24
9.5_EER_
12.7_IEER_
Before 1/1/2024
9.1_EER_
12.7_IEER_
On or after 1/1/24
VRF air cooled
(cooling mode)
240,000 Btu/h240,000 Btu/hVRF multisplit_system_
with heat recovery
9.3_EER_
12.5_IEER_
Before 1/1/2024
8.9_EER_
12.5_IEER_
On or after 1/1/24
9.3_EER_
12.5_IEER_
Before 1/1/2024
8.9_EER_
12.5_IEER_
On or after 1/1/24

a. VRF outdoor units can be combined with innumerable indoor unit combinations, which will vary by application, building type, building size, operating conditions, and comfort

level goals. Selection of indoor units tested during the test is considered to be representative of commonly sold applications and is detailed in AHRI 1230. Informative Note: For single-phase VRF multisplit system less than 65,000 Btu/h, see Informative Appendix F, Table F-1 for the U.S. Department of Energy minimum.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 121