Table 6.8.1-9 Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements (Continued)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
VRF water source
(cooling mode)
<65,000 Btu/hAllVRF multisplit_systems_
86°F entering water
12.0_EER_
16.0_IEER_
AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF water source
(cooling mode)
<65,000 Btu/hAllVRF multisplit_systems_
with heat recovery
86°F entering water
11.8_EER_
15.8_IEER_
11.8_EER_
15.8_IEER_
VRF water source
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
VRF multisplit_system_
86°F entering water
12.0_EER_
16.0_IEER_
12.0_EER_
16.0_IEER_
VRF water source
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
VRF multisplit_system_
with heat recovery
86°F entering water
11.8_EER_
15.8_IEER_
11.8_EER_
15.8_IEER_
VRF water source
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
VRF multisplit_system_
86°F entering water
10.0_EER_
14.0_IEER_
10.0_EER_
14.0_IEER_
VRF water source
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
VRF multisplit_system_
with heat recovery
86°F entering water
9.8_EER_
13.8_IEER_
9.8_EER_
13.8_IEER_
VRF water source
(cooling mode)
240,000 Btu/h240,000 Btu/hVRF multisplit_system_
86°F entering water
10.0_EER_
12.0_IEER_
10.0_EER_
12.0_IEER_
VRF water source
(cooling mode)
240,000 Btu/h240,000 Btu/hVRF multisplit_system_
with heat recovery
86°F entering water
9.8_EER_
11.8_IEER_
9.8_EER_
11.8_IEER_
VRF groundwater
source (cooling
mode)
<135,000 Btu/hAllVRF multisplit_system_
59°F entering water
16.2_EER_AHRI 1230- 2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF groundwater
source (cooling
mode)
<135,000 Btu/hAllVRF multisplit_system_
with heat recovery
59°F entering water
16.0_EER_16.0_EER_
VRF groundwater
source (cooling
mode)
135,000 Btu/h135,000 Btu/hVRF multisplit_system_
59°F entering water
13.8_EER_13.8_EER_
VRF groundwater
source (cooling
mode)
135,000 Btu/h135,000 Btu/hVRF multisplit_system_
with heat recovery
59°F entering water
13.6_EER_13.6_EER_
VRF ground source
(cooling mode)
<135,000 Btu/hAllVRF multisplit_system_
77°F entering water
13.4_EER_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF ground source
(cooling mode)
<135,000 Btu/hAllVRF multisplit_system_
with heat recovery
77°F entering water
13.2_EER_13.2_EER_
VRF ground source
(cooling mode)
135,000 Btu/h135,000 Btu/hVRF multisplit_system_
77°F entering water
11.0_EER_11.0_EER_
VRF ground source
(cooling mode)
135,000 Btu/h135,000 Btu/hVRF multisplit_system_
with heat recovery
77°F entering water
10.8_EER_10.8_EER_

a. VRF outdoor units can be combined with innumerable indoor unit combinations, which will vary by application, building type, building size, operating conditions, and comfort

level goals. Selection of indoor units tested during the test is considered to be representative of commonly sold applications and is detailed in AHRI 1230. Informative Note: For single-phase VRF multisplit system less than 65,000 Btu/h, see Informative Appendix F, Table F-1 for the U.S. Department of Energy minimum.

122 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)