ASHRAE-90.1-2022- - Page 125

Extracted Content

Table 6.8.1-9 Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements (Continued)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
VRF air cooled
(heating mode)
<65,000 Btu/h
(cooling capacity)
Three-phase for
applications in the U.S.
and single- and three-
phase for applications
outside the U.S.
VRF multisplit_system_7.7_HSPF_
Before 1/1/2023
On or after 1/1/2023
HSPF2 = 7.5
AHRI 1230-2014 with
Addendum 1
before 1/1/2023
AHRI 210/240-2023
on or after 1/1/2023
VRF air cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
47°F db/43°F wb
outdoor air
3.3_COPH_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF air cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.25_COPH_2.25_COPH_
VRF air cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
47°F db/43°F wb
outdoor air
3.2_COPH_3.2_COPH_
VRF air cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.05_COPH_2.05_COPH_
VRF water source
(heating mode)
<65,000 Btu/h
(cooling capacity)
VRF multisplit_system_
68°F entering water
4.3_COPH_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF water source
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
68°F entering water
4.3_COPH_4.3_COPH_
VRF water source
(heating mode)
135,000 Btu/h and
<240,000 Btu/h
(cooling capacity)
135,000 Btu/h and
<240,000 Btu/h
(cooling capacity)
VRF multisplit_system_
68°F entering water
4.0_COPH_4.0_COPH_
VRF water source
(heating mode)
240,000 Btu/h
(cooling capacity)
240,000 Btu/h
(cooling capacity)
VRF multisplit_system_
68°F entering water
3.9_COPH_3.9_COPH_
VRF groundwater
source (heating
mode)
<135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
50°F entering water
3.6_COPH_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF groundwater
source (heating
mode)
135,000 Btu/h
(cooling capacity)
135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
50°F entering water
3.3_COPH_3.3_COPH_
VRF ground source
(heating mode)
<135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
32°F entering water
3.1_COPH_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF ground source
(heating mode)
135,000 Btu/h
(cooling capacity)
135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
32°F entering water
2.8_COPH_2.8_COPH_

a. VRF outdoor units can be combined with innumerable indoor unit combinations, which will vary by application, building type, building size, operating conditions, and comfort

level goals. Selection of indoor units tested during the test is considered to be representative of commonly sold applications and is detailed in AHRI 1230. Informative Note: For single-phase VRF multisplit system less than 65,000 Btu/h, see Informative Appendix F, Table F-1 for the U.S. Department of Energy minimum.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 123