Table 6.8.1-15 Electrically Operated Water-Source Heat Pumps—Minimum Efficiency Requirements [ b]

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test
Procedurea
Water-to-air, water loop
(cooling mode)
<17,000 Btu/hAll86°F entering water12.2_EER_ISO 13256-1
Water-to-air, water loop
(cooling mode)
17,000 Btu/h and
<65,000 Btu/h
17,000 Btu/h and
<65,000 Btu/h
17,000 Btu/h and
<65,000 Btu/h
13.0_EER_13.0_EER_
Water-to-air, water loop
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
13.0_EER_13.0_EER_
Water-to-air, groundwater (cooling
mode)
<135,000 Btu/hAll59°F entering water18.0_EER_ISO 13256-1
Brine-to-air, ground loop (cooling
mode)
<135,000 Btu/hAll77°F entering water14.1_EER_ISO 13256-1
Water-to-water, water loop
(cooling mode)
<135,000 Btu/hAll86°F entering water10.6_EER_ISO 13256-2
Water-to-water, groundwater
(cooling mode)
<135,000 Btu/hAll59°F entering water16.3_EER_ISO 13256-2
Brine-to-water, ground loop
(cooling mode)
<135,000 Btu/hAll77°F entering water12.1_EER_ISO 13256-2
Water-to-air, water loop
(heating mode)
<135,000 Btu/h
(cooling capacity)
68°F entering water4.3_COPH_ISO 13256-1
Water-to-air, groundwater (heating
mode)
<135,000 Btu/h
(cooling capacity)
50°F entering water3.7_COPH_ISO 13256-1
Brine-to-air, ground loop (heating
mode)
<135,000 Btu/h
(cooling capacity)
32°F entering water3.2_COPH_ISO 13256-1
Water-to-water, water loop
(heating mode)
<135,000 Btu/h
(cooling capacity)
68°F entering water3.7_COPH_ISO 13256-1
Water-to-water, groundwater
(heating mode)
<135,000 Btu/h
(cooling capacity)
50°F entering water3.1_COPH_ISO 13256-2
Brine-to-water, ground loop
(heating mode)
<135,000 Btu/h
(cooling capacity)
32°F entering water2.5_COPH_ISO 13256-2

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Single-phase, U.S. air-cooled heat pumps <65,000 Btu/h are regulated as consumer products by 10 CFR 430. SEER, SEER2, HPSF and HPSF2 values for single-phase products

are set by the U.S. DOE. Informative Note: See Informative Appendix F for the U.S. DOE minimum.

130 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)