Table 6.8.1-17 Ceiling-Mounted Computer-Room Air Conditioners—Minimum Efficiency Requirements (Continued)

Equipment TypeStandard
Model
Net Sensible
Cooling Capacity
Minimum Net
Sensible COP
Rating Conditions
Return Air
(dry bulb/dew point)
Test Procedure
Water cooled with_fluid_
economizer
Ducted<29,000 Btu/h2.3375°F/52°F (Class 1)AHRI 1360
Water cooled with_fluid_
economizer
Ducted29,000 Btu/h and
<65,000 Btu/h
2.232.232.23
Water cooled with_fluid_
economizer
Ducted65,000 Btu/h2.132.132.13
Water cooled with_fluid_
economizer
Nonducted<29,000 Btu/h2.362.362.36
Water cooled with_fluid_
economizer
Nonducted29,000 Btu/h and
<65,000 Btu/h
2.262.262.26
Water cooled with_fluid_
economizer
Nonducted65,000 Btu/h2.162.162.16
Glycol cooledDucted<29,000 Btu/h1.9775°F/52°F (Class 1)AHRI 1360
Glycol cooledDucted29,000 Btu/h and
<65,000 Btu/h
1.931.931.93
Glycol cooledDucted65,000 Btu/h1.781.781.78
Glycol cooledNonducted<29,000 Btu/h2.002.002.00
Glycol cooledNonducted29,000 Btu/h and
<65,000 Btu/h
1.981.981.98
Glycol cooledNonducted65,000 Btu/h1.811.811.81
Glycol cooled with
fluid economizer
Ducted<29,000 Btu/h1.9275°F/52°F (Class 1)AHRI 1360
Glycol cooled with
fluid economizer
Ducted29,000 Btu/h and
<65,000 Btu/h
1.881.881.88
Glycol cooled with
fluid economizer
Ducted65,000 Btu/h1.731.731.73
Glycol cooled with
fluid economizer
Nonducted<29,000 Btu/h1.951.951.95
Glycol cooled with
fluid economizer
Nonducted29,000 Btu/h and
<65,000 Btu/h
1.931.931.93
Glycol cooled with
fluid economizer
Nonducted65,000 Btu/h1.761.761.76

Table 6.8.1-18 Walk-In Cooler and Freezer Display Door Efficiency Requirements

Class DescriptorClassMaximum Energy
Consumption, kWh/daya
Test Procedure
Display door, medium temperatureDD, M0.04 ×Add + 0.4110 CFR 431
Display door, low temperatureDD, L0.15 ×Add + 0.2910 CFR 431

a. Add is the surface area (ft [2] ) of the display door.

Table 6.8.1-19 Walk-In Cooler and Freezer Nondisplay Door Efficiency Requirements

Class DescriptorClassMaximum Energy
Consumption, kWh/daya
Test Procedure
Passage door, medium temperaturePD, M0.05 ×And + 1.710 CFR 431
Passage door, low temperaturePD, L0.14 ×And + 4.810 CFR 431
Freight door, medium temperatureFD, M0.04 ×And + 1.910 CFR 431
Freight door, low temperatureFD, L0.12_And_ + 5.610 CFR 431

a. And is the surface area (ft [2] ) of the non-display door.

134 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)