Table 6.8.1-20 Walk-In Cooler and Freezer Refrigeration System Efficiency Requirements

Class DescriptorClassMinimum Annual
Walk-In Energy Factor AWEF,
Btu/W·h a
Test
Procedure
Compliance Date:
Equipment Manufactured
Starting On
Dedicated condensing, medium
temperature, indoor system
DC.M.I5.61AHRI 1250June 5, 2017
Dedicated condensing, medium
temperature, outdoor system
DC.M.O7.60AHRI 1250June 5, 2017
Dedicated condensing, low
temperature, indoor system, net
capacity (qnet) < 6500 Btu/h
DC.L.I
<6500 Btu/h
9.091 × 10–5 ×qnet + 1.81AHRI 1250July 10, 2020
Dedicated condensing, low
temperature, indoor system, net
capacity (qnet)  6500 Btu/h
DC.L.I,
6500 Btu/h
2.40AHRI 1250July 10, 2020
Dedicated condensing, low
temperature, outdoor system, net
capacity (qnet) < 6500 Btu/h
DC.L.O,
<6500 Btu/h
6.522 × 10–5 ×qnet + 2.73AHRI 1250July 10, 2020
Dedicated condensing, low
temperature, outdoor system, net
capacity (qnet) 6500 Btu/h
DC.L.O,
6500 Btu/h
3.15AHRI 1250July 10, 2020
Unit cooler, mediumUC.M9.00AHRI 1250July 10, 2020
Unit cooler, low temperature, net
capacity (qnet) < 15,500 Btu/h
UC.L,
<15,500 Btu/h
1.575 × 10–5 ×qnet + 3.91AHRI 1250July 10, 2020
Unit cooler, low temperature, net
capacity (qnet)  15,500 Btu/h
UC.L,
15,500 Btu/h
4.15AHRI 1250July 10, 2020

a. qnet is net capacity (Btu/h) as determined in accordance with AHRI 1250.

Table 6.8.1-21 Ceiling FanEfficiency Requirements aCol3Col4
Equipment TypeSize CategoryMinimum EfficiencybTest Procedurec
Large-diameter ceiling fan
for applications outside the
U.S.
Blade span ≥ 84.5 in.CFEI ≥ 1.00 at high (maximum) speed; and
CFEI ≥ 1.31 at 40% of high speed or the nearest
speed that is not less than 40% of high speed
10 CFR 430 Appendix U
or AMCA Standard 230
and AMCA Standard 208

a. The minimum efficiency requirements at both high speed and 40% of maximum speed must be met or exceeded to comply with this standard. b. Ceiling fans are regulated in the U.S. as consumer products under 10 CFR 430. For U.S. applications of large-diameter ceiling fans, refer to Informative Appendix F, Table F-6,

for the U.S. DOE minimum efficiency requirements. c. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 135