Table 7.4-1 Performance Requirements for Water-Heating Equipment—Minimum Efficiency Requirements (Continued)

Equipment TypeSize Category
(Input)
Subcategory or
Rating Condition
Performance Required aTest
Procedureb,c
Oil storage
water heaters
105,000 Btu/h<4000(Btu/h)/gal
50 gal
For applications outside U.S., see footnote (h).
For U.S. applications, see footnote (g).
10 CFR 430
Appendix E
Oil storage
water heaters
105,000 Btu/h and
140,000 Btu/h e
120 gal
<4000 (Btu/h)/gal
180°F
Very small DP: UEF = 0.2932 – (0.0015 ×Vr)
Low DP: UEF = 0.5596 – (0.0018 ×Vr)
Medium DP: UEF = 0.6194 – (0.0016 ×Vr)
High DP: UEF = 0.6740 – (0.0013 ×Vr)
10 CFR 430
Appendix E
Oil storage
water heaters
>140,000 Btu/h<4000 (Btu/h)/gal80%Et
SL(Q/800 + 110
), Btu/h
V
10 CFR 431.106
Oil instantaneous
water heaters
210,000 Btu/h4000 (Btu/h)/gal
<2 gal
80%Et
EF  0.59 – 0.0005 ×V
10 CFR 430
Appendix E
Oil instantaneous
water heaters
>210,000 Btu/h4000 (Btu/h)/gal
<10 gal
80%Et10 CFR 431.106
Oil instantaneous
water heaters
>210,000 Btu/h4000 (Btu/h)/gal
10 gal
78%_Et _
SL(Q/800 + 110
), Btu/h
V
78%_Et _
SL(Q/800 + 110
), Btu/h
V
Hot-water supply
boilers, gas and oil f
300,000 Btu/h and
<12,500,000 Btu/h
4000 (Btu/h)/gal
<10 gal
80%Et10 CFR 431.106
Hot-water supply
boilers, gas f
300,000 Btu/h and
<12,500,000 Btu/h
4000 (Btu/h)/gal
10 gal
80%Et
SL(Q/800 + 110
), Btu/h
V
10 CFR 431.106
Hot-water supply
boilers, oil
300,000 Btu/h and
<12,500,000 Btu/h
4000 (Btu/h)/gal
10 gal
78%Et
SL(Q/800 + 110
), Btu/h
V
10 CFR 431.106
Pool heaters, gasAll82%Et for commercial_pool_ heaters and for
applications outside U.S. For U.S.
applications, see footnote (g).
10 CFR 430
Appendix P
Heat pump_pool_
heaters
All50°F db 44.2°F wb
outdoor air
80.0°F entering water
4.0_COP_10 CFR 430
Appendix P
Unfired storage tanksAllR-12.5(none)
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.

140 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)