8.7.3.2 Manuals. Construction documents shall require that an operating manual and maintenance manual be provided to the property owner. The manuals shall include, at a minimum, the following:

a. Submittal data stating equipment rating and selected options for each piece of equipment requiring main tenance. b. Operation manuals and maintenance manuals for each piece of equipment requiring maintenance.

Required routine maintenance actions shall be clearly identified. c. Names and addresses of at least one qualified service agency . d. A complete narrative of how each system is intended to operate.

Enforcement agencies should only check to ensure that the construction documents require this information to be transmitted to the owner and should not expect copies of any of the materials.

8.8 Product Information (Not Used)

8.9 Verification, Testing, and Commissioning 8.9.1 Verification and Testing. Building power distribution systems and applicable equipment shall be verified and tested in accordance with this section and provisions of Section 4.2.5.1. Testing shall verify that control elements are configured and operating in accordance with applicable requirements of

a. automatic receptacles controls (Section 8.4.2) and b. energy monitoring (Section 8.4.3).

Verification and FPT documentation shall comply with Section 4.2.5.1. 8.9.2 Commissioning. The energy performance of the power systems shall be commissioned in accordance with Section 4.2.5.2, and reporting shall comply with Section 4.2.5.2.2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 147