ASHRAE-90.1-2022- - Page 153
Extracted Content
Table 9.2.2.1 Exceptions to Interior Lighting Power and Minimum Control Requirements
| Item # | Equipment/Application | In Addition to and Controlled Separately from General Lighting | Required Controls |
|---|---|---|---|
| 1 | Lighting that is integral to_equipment_, medical_equipment_ or instrumentation, and is installed by its_manufacturer_ | YES | No control requirements |
| 2 | Power for only the germicidal function in_luminaires_ or sources | YES | No control requirements |
| 3 | Lighting specifically designed for use only during medical or dental procedures | YES | 9.4.1.1(a)—Local control |
| 4 | Lighting specifically designed for the research or support of nonhuman life forms except for horticultural production or cultivation | YES | 9.4.1.1(a)—Local control |
| 5 | Lighting for video broadcasting, video or film production, or live performance | YES | 9.4.1.1(a)—Local control |
| 6 | Lighting that is an integral part of advertising or directional signage | YES | 9.4.1.1(i)—Scheduled shutoff |
| 7 | Lighting integral to both open and glass-enclosed refrigerator and freezer cases | YES | 9.4.1.1(h)—Automatic fullOFF or 9.4.1.1(i)—Scheduled shutoff |
| 8 | Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions | YES | 9.4.1.1(a)—Local control and 9.4.1.1(i)—Scheduled shutoff |
| 9 | Display or accent lighting that is an essential element for the function performed in galleries, museums, and monuments | YES | 9.4.1.1(a)—Local control and either 9.4.1.1(h)—Automatic fullOFF or 9.4.1.1(i)—Scheduled shutoff |
| 10 | Lighting integral to food warming and food preparation equipment | YES | 9.4.1.1(a)—Local control and either 9.4.1.1(h)—Automatic fullOFF or 9.4.1.1(i)—Scheduled shutoff |
| 11 | Lighting that is for sale or lighting educational demonstration systems | YES | 9.4.1.1(a)—Local control and either 9.4.1.1(h)—Automatic fullOFF or 9.4.1.1(i)—Scheduled shutoff |
| 12 | Mirror lighting in makeup or dressing areas used for theatrical or broadcast functions | YES | 9.4.1.1(a)—Local control and either 9.4.1.1(h)—Automatic fullOFF or 9.4.1.1(i)—Scheduled shutoff |
| 13 | Accent lighting in religious pulpit and choir areas | YES | 9.4.1.1(a)—Local control and either 9.4.1.1(h)—Automatic fullOFF or 9.4.1.1(i)—Scheduled shutoff |
| 14 | Lighting in interior_spaces_ that have been specifically designated as a registered interior_historic_ landmark | NO | 9.4.1.1(a)—Local control and either 9.4.1.1(h)—Automatic fullOFF or 9.4.1.1(i)—Scheduled shutoff |
| 15 | Furniture-mounted supplemental_task lighting_ | YES | 9.4.1.1(a)—Local control and 9.4.1.1(h)—Automatic fullOFF |
ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 151