Table 9.2.2.1 Exceptions to Interior Lighting Power and Minimum Control Requirements

Item #Equipment/ApplicationIn Addition to and
Controlled Separately
from General Lighting
Required Controls
1Lighting that is integral to_equipment_, medical_equipment_ or
instrumentation, and is installed by its_manufacturer_
YESNo control requirements
2Power for only the germicidal function in_luminaires_ or sourcesYESNo control requirements
3Lighting specifically designed for use only during medical or
dental procedures
YES9.4.1.1(a)—Local control
4Lighting specifically designed for the research or support of
nonhuman life forms except for horticultural production or
cultivation
YES9.4.1.1(a)—Local control
5Lighting for video broadcasting, video or film production, or live
performance
YES9.4.1.1(a)—Local control
6Lighting that is an integral part of advertising or directional
signage
YES9.4.1.1(i)—Scheduled shutoff
7Lighting integral to both open and glass-enclosed refrigerator and
freezer cases
YES9.4.1.1(h)—Automatic fullOFF
or
9.4.1.1(i)—Scheduled shutoff
8Lighting in retail display windows, provided the display area is
enclosed by ceiling-height partitions
YES9.4.1.1(a)—Local control and
9.4.1.1(i)—Scheduled shutoff
9Display or accent lighting that is an essential element for the
function performed in galleries, museums, and monuments
YES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
10Lighting integral to food warming and food preparation
equipment
YES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
11Lighting that is for sale or lighting educational demonstration
systems
YES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
12Mirror lighting in makeup or dressing areas used for theatrical or
broadcast functions
YES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
13Accent lighting in religious pulpit and choir areasYES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
14Lighting in interior_spaces_ that have been specifically designated
as a registered interior_historic_ landmark
NO9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
15Furniture-mounted supplemental_task lighting_YES9.4.1.1(a)—Local control
and
9.4.1.1(h)—Automatic fullOFF

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 151