ASHRAE-90.1-2022- - Page 155

Extracted Content

Table 9.3.1-1 Simplified Building Method for Office BuildingsCol2
Interior Space Type and LPAControls
All_spaces_ in office_buildings_ other than parking garages
The total_LPA_for the_ building_other than parking garages shall not
exceed 0.56 W/ft2.
All lighting shall be_automatically_controlled to turn off when
individual_spaces_are either unoccupied or scheduled to be
unoccupied. (Exception: Lighting load not exceeding 0.02 W/ft2
multiplied by the gross lighted area of the_space_ shall be permitted to
operate at all times.)
Each_space_ shall have a_manual control device_ that allows the
occupant to reduce lighting power by a minimum of 50% and to turn
the lighting off.
Office_spaces_ 150 ft2, classrooms, conference rooms, meeting
rooms, training rooms, storage rooms, and break rooms
These_spaces_ shall also be controlled by_manual_-ON occupant
sensors.
Office_spaces_ >150 ft2 and restroomsThese_spaces_ shall also be controlled by_occupant sensors_.
Stairwells and corridors in office_buildings_These_spaces_ shall also be controlled by_occupant sensors_ that
reduce the lighting power by a minimum of 50% when no activity is
detected for not longer than 15 minutes and be controlled to turn off
when the_building_ is either unoccupied or scheduled to be
unoccupied.
Parking garages: The_LPA_shall not exceed 0.14 W/ft2 for the interior
parking floors.
Uncovered floors of a garage shall use_LPA_and control requirements
in Table 9.3.2 for parking lots.
All lighting shall be controlled by_occupant sensors_. Controls shall
reduce the power by a minimum of 50% when no activity is detected
for not longer than 15 minutes. No device shall_control_ more than
3600 ft2.
Table 9.3.1-2 Simplified Building Method for Retail BuildingsCol2
Interior Space TypeControls
All_spaces_ in retail_buildings_ other than parking garages
The total_LPA_for the_building_other than parking garages shall not
exceed 0.70 W/ft2.
All lighting shall be_automatically_controlled to turn off when
individual_spaces_are either unoccupied or scheduled to be
unoccupied. (Exception: Lighting load not exceeding 0.02 W/ft2
multiplied by the gross lighted area of the_space_ shall be permitted to
operate at all times.)
Each_space_ shall have a_manual_ control device that allows the
occupant to reduce lighting power by a minimum of 50% and to turn
the lighting off.
Sales areaThese_spaces_ shall also be_automatically_controlled to
• reduce the_general lighting_ power by a minimum of 75% during
nonbusiness hours,
• to turn off all lighting other than_general lighting_ during nonbusi-
ness hours, and
• by_continuous daylight dimming_ controls in_spaces_ with_toplighting_.
Stock rooms, dressing/fitting rooms, locker rooms, and restroomsThese_spaces_ shall also be controlled by; auto-ON or_manual_-ON
occupant sensors, and_continuous daylight dimming_ controls in
spaces with_toplighting_.
Office_spaces_, conference rooms, meeting rooms, training rooms,
storage rooms, break rooms, and utility_spaces_
These_spaces_ shall also be controlled by;manual-ON occupant
sensors, and_continuous daylight dimming_ controls in_spaces_ with
toplighting.
Stairwells and corridors in retail_buildings_These_spaces_ shall also be controlled by_occupant sensors_ that
reduce the lighting power by a minimum of 50% when no activity is
detected for not longer than 15 minutes and be controlled to turn off
when the_building_is either unoccupied or scheduled to be
unoccupied.
Parking garages: The_LPA_shall not exceed 0.14 W/ft2 for the
interior parking floors.
Uncovered floors of a garage shall use_LPA_and control requirements
in Table 9.3.2 for parking lots.
All lighting shall be controlled by_occupant sensors_. Controls shall
reduce the power by a minimum of 50% when no activity is detected
for not longer than 15 minutes. No device shall_control_ a more than
3600 ft2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 153