Table 9.3.1-3 Simplified Building Method for School Buildings

Interior Space TypeControls
All_spaces_ in school_buildings_ other than parking garages
The total_LPA_for the_building_other than parking garages shall not
exceed 0.63 W/ft2
All lighting shall be_automatically_controlled to turn off when
individual_spaces_are either unoccupied or scheduled to be unoccupied.
(Exception: Lighting load not exceeding 0.02 W/ft2 multiplied by the
gross lighted area of the_space_ shall be permitted to operate at all
times.)
Each_space_ shall have a_manual_ control device that allows the occupant
to reduce lighting power by a minimum of 50% and to turn the lighting
off.
Classrooms, offices_spaces_, conference rooms, meeting rooms,
library, storage rooms, and break rooms
These_spaces_ shall also be controlled by_manual_-ON occupant sensors.
Gymnasiums and cafeteriasThese_spaces_ shall also be controlled by_occupant sensors_.
RestroomsThese_spaces_ shall also be controlled by_occupant sensors_.
Stairwells and corridors in school_buildings_ and parking garagesThese_spaces_ shall also be controlled by_occupant sensors_ that reduce
the lighting power by a minimum of 50% when no activity is detected
for not longer than 15 minutes and be controlled to turn off when the
_building_is either unoccupied or scheduled to be unoccupied.
Parking Garages: The_LPA_shall not exceed 0.14 W/ft2 for the
interior parking floors.
Uncovered floors of a garage shall use_LPA_and control
requirements in Table 9.3.2 for parking lots.
All lighting shall be controlled by_occupant sensors_. Controls shall
reduce the power by a minimum of 50% when no activity is detected
for not longer than 15 minutes. No device shall_control_ a more than
3600 ft2.

Table 9.3.2 Simplified Building Method for Building Exteriors

Exterior Area TypeExterior
Lighting Power
Allowance a,b
Controls
All exterior areasAll lighting shall be_automatically_controlled to shut off the lighting when daylight is
available.
Base allowance200 WLuminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
Façade lighting0.10 W/ft2Luminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
Roof terraces, special
feature areas, walkways,
plazas and ramps
0.07 W/ft2_Luminaires_shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
Landscape0.036 W/ft2Luminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
Entry doors14 W/linear ftLuminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
StairsExemptNo additional controls required.
Parking lots and drives0.037 W/ft2Luminaires mounted 25 ft or less above_grade_ shall be controlled to reduce the power by at
least 50% when no activity is detected for not longer than 15 minutes.
All other areas not listed0.20 W/ft2Luminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.

a. To calculate the exterior allowance, multiply the space or area square footage by the allowed W/ft [2] and sum the exterior allowances and the base allowance. Façade lighting shall

be calculated separately by multiplying the facade area by the allowed W/ft [2] . Façade allowance shall not be traded with other exterior areas or between separate facade areas . b. For buildings in Lighting Zone 2, as defined in Table 9.4.2-1, multiply exterior allowances by 0.7. For buildings in Lighting Zone 4, as defined in Table 9.4.2-1, multiply exterior

allowances by 1.4.