ASHRAE-90.1-2022- - Page 160

Extracted Content

Table 9.4.2-2 Individual Lighting Power Allowances for Building Exteriors Applications

Base Site Allowance (Base allowance may be used in tradable or non-tradable surfaces.)

No allowance 160 W 280 W 400 W 560 W

Tradable Surfaces ( LPD for uncovered parking areas, building grounds, building entrances, exits and loading docks, canopies and overhangs, and outdoor sales areas may be traded.)

Uncovered Parking Areas

Parking areas and drivesNo allowance0.015 W/ft20.026W/ft20.037 W/ft20.052 W/ft2(b) and either
(d) or (e)
Parking areas and drives with
luminaires >78W and mounting
height <24 ft
No allowance0.015 W/ft20.026 W/ft20.037 W/ft20.052 W/ft2(b) and (e)
GroundsCol2Col3Col4Col5Col6Col7
Walkways/rampsNo allowance0.5 W/linear ft0.5 W/linear ft0.55W/linear ft0.60 W/linear
ft
(b) and either
(d) or (e)
Plaza areasNo allowance0.028 W/ft20.049 W/ft20.070 W/ft20.098 W/ft2(b) and either
(d) or (e)
Roof terraces and special featuresNo allowance0.04 W/ft20.07 W/ft20.10 W/ft20.140 W/ft2(b) and either
(d) or (e)
Dining areasNo allowance0.156 W/ft20.273 W/ft20.390 W/ft20.546 W/ft2(b) and either
(d) or (e)
Pedestrian tunnelsNo allowance0.063 W/ft20.110 W/ft20.157 W/ft20.220 W/ft2(d) or (e)
LandscapingNo allowance0.014 W/ft20.025 W/ft20.036 W/ft20.050 W/ft2(b) and (c)

Building Entrances, Exits, and Loading Docks

Pedestrian and vehicular entrances
and exits
No allowance5.6 W/linear ft
of opening
9.8W/linear ft
of opening
14.0 W/linear
ft of opening
19.6 W/linear
ft of opening
(b) and either
(d) or (e)
Entry canopiesNo allowance0.072 W/ft20.126 W/ft20.180 W/ft20.252 W/ft2(b) and either
(d) or (e)
Loading docksNo allowance0.104 W/ft20.182 W/ft20.260 W/ft20.364 W/ft2(b) and either
(d) or (e)

Sales Canopies

Outdoor SalesCol2Col3Col4Col5Col6Col7
Open areas (including vehicle sales
lots)
No allowance0.072 W/ft20.126 W/ft20.180 W/ft20.252 W/ft2(b) and either
(d) or (e)
Street frontage for vehicle sales lots in
addition to “open area” allowance
No allowanceNo allowance7.2 W/linear ft10.3 W/linear
ft
14.4 W/linear
ft
(b) and either
(d) or (e)

Nontradable Surfaces ( LPD for the following applications can be used only for the specific application and cannot be traded between surfaces or with other exterior lighting. The following allowances are in addition to any allowance otherwise permitted in the “Tradable Surfaces” section of this table.)

Stairways Exempt Exempt Exempt Exempt Exempt (b)

158 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)