Table 9.4.2-2 Individual Lighting Power Allowances for Building Exteriors Applications (Continued)

Col1Zone 0Zone 1Zone 2Zone 3Zone 4Section
9.4.1.4
Required
Controls
Building_facades
(The allowance for each illuminated
facade_orientation_shall be calculated
by multiplying the allowable value by
the entire_facade area
or facades
length for that_orientation_.)
No allowance0.056 /ft2 of
facade area or
1.4 W/linear ft
of facade
length
0.098 W/ft2 of
_facade area_or
2.4 W/linear ft
of facade
length
0.140 W/ft2 of
_facade area_or
3.4 W/ linear ft
of facade
length
0.196 W/ft2 of
_facade area_or
4.8 W/linear ft
of facade
length
(b) and (c)
Automated teller machines and night
depositories
No allowance90 W per
location plus
35 W per
additional
ATM per
location
90 W per
location plus
35 W per
additional
ATM per
location
90 W per
location plus
35 W per
additional
ATM per
location
90 W per
location plus
35 W per
additional
ATM per
location
(b)
Uncovered entrances and gatehouse
inspection stations at guarded
facilities
No allowance0.144 W/ft20.252 W/ft20.360 W/ft20.504 W/ft2(b) and either
(d) or (e)
Uncovered loading areas for law
enforcement, fire, ambulance, and
other emergency service vehicles
No allowance0.104 W/ft20.182 W/ft20.260 W/ft20.364 W/ft2(b) and either
(d) or (e)
Drive-through windows/doorsNo allowance53 W per
drive-through
92 W per
drive-through
132 W per
drive-through
185 W per
drive-through
(b) and either
(d) or (e)
Parking near 24-hour retail entrancesNo allowance80 W per
main entry
140 W per
main entry
200 W per
main entry
280 W per
main entry
(b) and either
(d) or (e)
For areas that are not listed in this
table or are not comparable to areas
listed in this table, use the comparable
interior_space_type from Tables
9.5.2.1-1 and 9.5.2.1-2 as modified by
factors in this row.
No allowance22% of the
interior
lighting power
allowance
value
39% of the
interior
lighting power
allowance
value
55% of the
interior
lighting power
allowance
value
77% of the
interior
lighting power
allowance
value
(b) and either
(d) or (e)
Roadway/parking entry, trail head,
and toilet facility, or other locations
approved by the_authority having_
jurisdiction.
A single
_luminaire_of 10
W or less
No additional
allowance
No additional
allowance
No additional
allowance
No additional
allowance
(b) and either
(d) or (e)

Horticultural lighting in greenhouse spaces shall be controlled by a device that automatically turns off the horticultural lighting at specific programmed times.

9.4.4.2 Luminaires in indoor grow spaces used for horticultural lighting shall have a PPE of at least 1.9 µmol/J for integrated, nonserviceable luminaires, or a PPE of at least 1.9 µmol/J for lamps in lumi- naires with removable or serviceable lamps . Horticultural lighting in indoor grow spaces shall be controlled by a device that automatically turns off the horticultural lighting at specific programmed times.

Exception to 9.4.4.2: Indoor grow buildings with less than 40 kW of connected load for horticultural

lighting shall have a PPE of at least 1.7 µmol/J for integrated, nonserviceable luminaires, or a PPE of at least 1.7 µmol/J for lamps in luminaires with removable or serviceable lamps .

9.5 Prescriptive Compliance Path. Interior lighting power shall comply with either Section 9.5.1 or 9.5.2. Lighting control requirements shall comply with Section 9.4.1 and Tables 9.5.2.1-1 and 9.5.2.1-2.

9.5.1 Building Area Method Compliance Path . Use the following steps to determine the interior light- ing power allowance by the Building Area Method:

a. Determine the appropriate building area type from Table 9.5.1 and the corresponding LPD allowance. For

building area types not listed, selection of a reasonably equivalent type shall be permitted. b. Determine the gross lighted floor area in ft [2] of the building area type. c. Multiply the gross lighted floor areas of the building area types times the LPD .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 159