ASHRAE-90.1-2022- - Page 162

Extracted Content

Table 9.5.1 Lighting Power Density Allowances Using the Building Area Method

Building Area TypeaLPD, W/ft2
Automotive facility0.73
Convention center0.64
Courthouse0.75
Dining: Bar lounge/leisure0.74
Dining: Cafeteria/fast food0.70
Dining: Family0.65
Dormitory0.52
Exercise center0.72
Fire station0.56
Gymnasium0.75
Health care clinic0.77
Hospital0.92
Hotel/motel0.53
Library0.83
Manufacturing facility0.82
Motion picture theater0.43
Multifamily0.46
Museum0.56
Office0.62
Parking garage0.17
Penitentiary0.65
Performing arts theater0.82
Police station0.62
Post office0.64
Religious facility0.66
Retail0.78
School/university0.70
Sports arena0.73
Town hall0.67
Transportation0.56
Warehouse0.45
Workshop0.86

a. In cases where both a general building area type and a specific building area type are listed, the specific building area type shall apply.

d. The interior lighting power allowance for the building is the sum of the lighting power allowances of all

building area types. Trade-offs among building area types are permitted, provided that the total installed interior lighting power does not exceed the interior lighting power allowance .

9.5.2 Space-by-Space Method Compliance Path

9.5.2.1 Space-by-Space Method of Calculating Interior Lighting Power Allowance. Use the following steps to determine the interior lighting power allowance by the Space-by-Space Method:

160 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)