ASHRAE-90.1-2022- - Page 166

Extracted Content

Table 9.5.2.1-1 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

Informative Note: This table covers common space types typically found in multiple building types. Table 9.5.2.1-2 covers building -specific space types typically found in a single building type.

LPD, Common Space Types [a] W/ft [2] RCR

Atrium

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

<20 ft in height 0.32 NA REQ ADD1 ADD1 REQ REQ ADD2 ADD2

 20 ft and  40 ft in height 0.41 NA REQ ADD1 ADD1 REQ REQ ADD2 ADD2

40 ft in height 0.51 11 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Audience Seating Area

Auditorium 0.57 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Gymnasium 0.23 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Motion picture theater 0.27 4 REQ ADD1 ADD1 REQ ADD2 ADD2

Performing arts theater 1.10 8 REQ ADD1 ADD1 REQ ADD2 ADD2

Sports arena 0.27 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

All other audience seating areas 0.23 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Banking Activity Area 0.56 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Classroom/Lecture Hall/Training Room

Shop classroom 1.17 6 REQ ADD1 ADD1 REQ REQ REQ

All other classrooms/lecture halls/training rooms 0.72 4 REQ ADD1 ADD1 REQ REQ REQ REQ

Computer Room 0.75 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Conference/Meeting/Multipurpose Rooms 0.88 6 REQ ADD1 ADD1 REQ REQ REQ REQ

Control/Editing Room or Booth 0.73 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Copy/Print Room 0.56 6 REQ ADD1 ADD1 REQ REQ REQ

Corridor 0.44 width <8 ft REQ REQ REQ REQ ADD2 ADD2

Courtroom 1.08 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Dining Areas

Bar/lounge or leisure dining 0.76 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

a. Where both a common space type and a building -specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-2 for building -specific space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.