ASHRAE-90.1-2022- - Page 167

Extracted Content

Table 9.5.2.1-1 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

Informative Note: This table covers common space types typically found in multiple building types. Table 9.5.2.1-2 covers building -specific space types typically found in a single building type.

LPD, Common Space Types [a] W/ft [2] RCR

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Cafeteria or fast-food dining 0.36 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Family dining 0.52 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

All other dining areas 0.42 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Electrical/Mechanical Room 0.71 6 REQ

Emergency Vehicle Garage 0.51 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Equipment Room 0.73 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Food Preparation Area 1.19 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Guest Room 0.41 6 See Section 9.4.1.3(b).

Laboratory

In or as a classroom 1.05 6 REQ ADD1 ADD1 REQ REQ REQ REQ ADD2 ADD2

All other laboratories 1.21 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Laundry/Washing Area 0.51 4 REQ ADD1 ADD1 REQ REQ REQ REQ

Loading Dock, Interior 0.87 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Lobby

Elevator 0.64 6 REQ REQ REQ ADD2 ADD2

Hotel 0.48 4 REQ REQ REQ ADD2 ADD2

Motion picture theater 0.20 4 REQ REQ REQ ADD2 ADD2

Performing arts theater 1.21 6 REQ REQ REQ ADD2 ADD2

All other lobbies 0.80 4 REQ REQ REQ REQ ADD2 ADD2

Locker Room 0.43 6 REQ ADD1 ADD1 REQ REQ REQ REQ

Lounge/Breakroom

Mother’s/wellness room 0.68 6 REQ ADD1 ADD1 REQ REQ

All other lounges/breakrooms 0.55 4 REQ ADD1 ADD1 REQ REQ REQ REQ

a. Where both a common space type and a building -specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-2 for building -specific space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.