ASHRAE-90.1-2022- - Page 168
Extracted Content
Table 9.5.2.1-1 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method
The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:
Informative Note: This table covers common space types typically found in multiple building types. Table 9.5.2.1-2 covers building -specific space types typically found in a single building type.
LPD, Common Space Types [a] W/ft [2] RCR
Office
(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.
Auto Full OFF
Daylight Response
Sidelight
Daylight Response
Toplight
Auto Reduction
(Full OFF complies)
Local Control
Manual
ON
Partial Auto ON
Multilevel
Lighting
Control
Scheduled
Shutoff
9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)
Office 150 ft [2] 0.73 8 REQ ADD1 ADD1 REQ REQ
Office >150 and 300 ft [2] 0.66 8 REQ ADD1 ADD1 REQ REQ
Offices >300 ft [2] 0.56 4 REQ ADD1 ADD1 REQ REQ REQ REQ REQ
Parking Garage
Daylight transition zone 1.06 4 See Section 9.4.1.2.
All other parking and drive areas 0.11 4 See Section 9.4.1.2.
Pharmacy Area 1.59 6 REQ ADD1 ADD1 REQ ADD2 ADD2
Restroom 0.74 8 REQ
Sales Area (For accent lighting, see Section 9.5.2.2[b].) 0.85 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2
Seating Area, General 0.21 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2
Security Screening
Airport/bus/ship/train/transportation screening 0.93 6 REQ REQ REQ ADD2 ADD2
Airport/bus/ship/train/transportation screening queue 0.56 6 REQ REQ REQ ADD2 ADD2
General security screening 0.64 6 REQ REQ REQ ADD2 ADD2
Stairway The space containing the stairway shall determine the LPD and control requirements for the stairway.
Stairwell 0.47 10 REQ REQ REQ ADD2 ADD2
Storage Room
<50 ft [2] 0.49 9 REQ REQ REQ
50 ft [2] 0.35 6 REQ REQ
Vehicular Maintenance Area 0.59 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2
Workshop (including workshop classrooms) 1.17 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2
a. Where both a common space type and a building -specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-2 for building -specific space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.