Table 9.5.2.1-2 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

Informative Note: This table covers building- specific space types typically found in a single building type. Table 9.5.2.1-1 covers common space types typically found in multiple building types.

LPD, Building-Specific Space Types [a] W/ft [2] RCR

Casino—Gaming Area

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Betting/sportsbook/keno/bingo area 0.82 5 REQ ADD2 ADD2

High-limit game area 1.68 4 REQ ADD2 ADD2

Slot machine/digital gaming area 0.54 5 REQ ADD2 ADD2

Table games area 1.09 5 REQ ADD2 ADD2

Convention Center—Exhibit Space 0.50 4 REQ ADD1 ADD1 REQ REQ REQ REQ

Correctional Facilities

Audience seating area 0.56 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Classroom/lecture hall/training room 0.74 4 REQ ADD1 ADD1 REQ REQ REQ

Confinement cells 0.60 6 REQ REQ

Dining area 0.35 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Dormitory—Living Quarters 0.48 8 REQ

Facility for the Visually Impaired  (A facility for the visually impaired is a facility that can be documented as being designed to comply with the light levels in ANSI/IES RP-28 and that is or will be licensed by local/state authorities for senior long-term care, adult daycare, senior support, and/or people with special visual needs.)

Chapel (used primarily by residents) 0.58 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Corridor (used primarily by residents) 0.71 width <8 ft REQ REQ REQ REQ ADD2 ADD2

Dining (used primarily by residents) 1.22 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Lobby 1.44 4 REQ REQ REQ REQ ADD2 ADD2

Recreation room/common living room  (used primarily by residents)

1.20 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Restroom (used primarily by residents) 0.96 8 REQ REQ REQ

Fire Station—Sleeping Quarters 0.22 6 REQ

a. Where both a common space type and a building specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-1 for common space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.