ASHRAE-90.1-2022- - Page 170

Extracted Content

Table 9.5.2.1-2 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

Informative Note: This table covers building- specific space types typically found in a single building type. Table 9.5.2.1-1 covers common space types typically found in multiple building types.

LPD, Building-Specific Space Types [a] W/ft [2] RCR

Gymnasium/Fitness Center

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Exercise area 0.82 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Playing area 0.82 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Health Care Facility

Control room (MRI/CT/radiology/PET) 0.78 8 REQ REQ REQ REQ

Exam/treatment room 1.33 8 REQ REQ REQ REQ ADD2 ADD2

Hospital corridor 0.61 width <8 ft REQ REQ REQ ADD2 ADD2 ADD2

Imaging room 0.94 6 REQ REQ ADD2 ADD2

Lounge 0.77 6 REQ ADD1 ADD1 REQ REQ REQ REQ

Medical supply room 0.56 6 REQ ADD1 ADD1 REQ

Nursery 0.87 6 REQ REQ REQ REQ ADD2 ADD2

Nurse’s station 1.07 6 REQ REQ REQ REQ ADD2 ADD2

Operating room 2.31 6 REQ REQ

Patient room 0.78 6 REQ REQ

Physical therapy room 0.82 6 REQ REQ REQ REQ ADD2 ADD2

Recovery room 1.18 6 REQ REQ ADD2 ADD2

Telemedicine 1.44 8 REQ ADD1 ADD1 REQ REQ REQ REQ

Library

Reading area 0.86 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Stacks 1.18 4 REQ ADD1 ADD1 REQ ADD2 ADD2

Manufacturing Facility

Detailed manufacturing area 0.75 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Extra-high bay area (>50 ft floor -to-ceiling height) 1.36 8 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

a. Where both a common space type and a building specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-1 for common space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.