Table 9.5.2.1-2 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

Informative Note: This table covers building- specific space types typically found in a single building type. Table 9.5.2.1-1 covers common space types typically found in multiple building types.

LPD, Building-Specific Space Types [a] W/ft [2] RCR

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

High bay area (25 to 50 ft floor -to-ceiling height) 1.24 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Low bay area (<25 ft floor -to-ceiling height) 0.85 3 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Museum

General exhibition area 0.31 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Restoration area 1.24 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Performing Arts Theater—Dressing Room 0.39 6 REQ ADD1 ADD1 REQ REQ

Post Office—Sorting Area 0.71 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Religious Facility

Audience seating area 0.72 4 REQ REQ REQ REQ ADD2 ADD2

Fellowship hall 0.50 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Worship/pulpit/choir area 0.75 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Retail Facilities

Dressing/fitting room 0.45 8 ADD2 ADD2

Hair care 0.65 6 REQ ADD1 ADD1 ADD2 ADD2

Mall concourse 0.57 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Massage 0.81 8 REQ ADD1 ADD1 REQ ADD2 ADD2

Nail care 0.75 6 REQ ADD1 ADD1 ADD2 ADD2

Sports Arena—Playing Area (Class of play as defined by ANSI/IES RP-6)

Class I facility 2.86 4 REQ REQ REQ REQ REQ

Class II facility 1.98 4 REQ REQ REQ REQ REQ

Class III facility 1.29 4 REQ REQ REQ REQ REQ

Class IV facility 0.85 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

a. Where both a common space type and a building specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-1 for common space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.