Table 9.5.2.2 Additional Lighting Power

Section 9.4.1.1(j)

9.5.2.1-2 space types for required controls.

Notes:

DescriptionAdditional Lighting Power
Decorative0.70 W/ft2
Retail sales750 W + (Retail Area 1 × 0.40 W/ft2) + (Retail Area 2 × 0.40 W/ft2) +
(Retail Area 3 × 0.70 W/ft2) + (Retail Area 4 × 1.00 W/ft2)
Video conferencing0.50 W/ft2

Retail Area 1 = the floor area for all products not listed in Retail Areas 2, 3, or 4 Retail Area 2 = the floor area used for the sale of vehicles, sporting goods, and small electronics Retail Area 3 = the floor area used for the sale of furniture, clothing, cosmetics, and artwork Retail Area 4 = the floor area used for the sale of jewelry, crystal, and china

Table 9.5.2.3 Control Factors Used in Calculating Additional Interior Lighting Power Allowance

Additional Control Method 
(in Addition to Mandatory Requirements)
Space TypeCol3Col4Col5Col6
Additional Control Method
(in Addition to Mandatory Requirements)
Open
Office
Private
Office
Conference
Room,
Meeting Room,
Classroom
(Lecture/
Training)
Retail
Sales
Area
Lobby, Atrium,
Dining Area,
Corridors/
Stairways, Gym/
Pool, Mall
Concourse,
Parking Garage
Programmable multilevel dimming control using programmable
time scheduling
0.050.050.100.100.10
Occupancy sensors controlling the downlight component of
workstation specific_luminaires_ with continuous dimming to off
capabilities
0.25a0000
Occupancy sensors controlling the downlight component of
workstation specific_luminaires_ with continuous dimming to off
operation, in combination with personal continuous dimming
control of downlight illumination by workstation occupant
0.30a,b0000

a. Control factor is limited to workstation-specific luminaires in partitioned single occupant work spaces contained within an open office environment (i.e. direct-indirect luminaires

with separately controlled downlight and uplight components, with the downward component providing illumination to a single occupant in an open plan workstation). Within 30 minutes of the occupant leaving the space, the downward component shall continuously dim to off over a minimum of two minutes. Upon the occupant entering the space, the downward component shall turn on at the minimum level and continuously raise the illumination to a preset level over a minimum of 30 seconds. The uplight component of workstation specific luminaire shall comply with Section 9.4.1.1(h) ( automatic full OFF). b. In addition to the requirements described in footnote (a), the control shall allow the occupant to select their preferred light level via a personal computer, handheld device, or simi larly accessible device located within the workstation.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 171