12
Table 11.5.1-1 Energy Credit Requirements by Building Use Type
| Building Use Type a | Climate Zone | Col3 | Col4 | Col5 | Col6 | Col7 | Col8 | Col9 | Col10 | Col11 | Col12 | Col13 | Col14 | Col15 | Col16 | Col17 | Col18 | Col19 | Col20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Building Use Typea | 0A | 0B | 1A | 1B | 2A | 2B | 3A | 3B | 3C | 4A | 4B | 4C | 5A | 5B | 5C | 6A | 6B | 7 | 8 |
| Multifamilyb | 50 | 50 | 50 | 50 | 50 | 50 | 46 | 50 | 50 | 48 | 50 | 46 | 50 | 50 | 49 | 50 | 50 | 50 | 50 |
| Health carec | 50 | 46 | 47 | 46 | 47 | 45 | 49 | 47 | 50 | 46 | 46 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
| Hotel/motel | 50 | 45 | 47 | 46 | 49 | 48 | 46 | 47 | 50 | 48 | 50 | 50 | 47 | 46 | 47 | 49 | 46 | 50 | 50 |
| Officed | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
| Restaurante | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
| Retail | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 49 | 50 | 47 | 48 | 45 | 42 | 46 |
| Educationf | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 46 |
| Warehouseg | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
| Otherh | 39 | 36 | 37 | 37 | 35 | 34 | 30 | 32 | 33 | 28 | 32 | 30 | 29 | 31 | 30 | 29 | 30 | 29 | 29 |
a. All building use types include supporting functions such as corridors, break rooms, lobbies, restrooms, mechanical rooms, storage rooms, conference rooms, individual equipment
and computer rooms with loads ≤10 kW, minor snack and beverage service without a commercial kitchen, and up to 10% of gross floor area of other building use types such as an office area less than 2000 ft [2] in a nonoffice building use type. b. “Multifamily” includes apartments, condominiums, dormitories, retirement living facilities, nontransient lodging, and residential portions of institutional care facilities, excluding
prisons. c. “Health Care” includes buildings within the scope of ASHRAE Standard 170 ventilation requirements that are dedicated to patient care, including related support areas of health
care facilities, hospitals, nursing facilities, outpatient facilities, and surgery centers. d. Office includes offices or clinics where medical, dental, psychotherapy, physical therapy or other services are provided that are not within the scope of ASHRAE Standard 170
ventilation requirements. e. Restaurants with commercial kitchens and dining areas that are separate buildings or constructed under separate permits shall meet restaurant building use type requirements. Where
restaurants are part of a larger building and are not seeking credit for either measure W01, W02, W03, or Q02, their area is permitted to be included with the larger building use type. f. Education includes schools, lecture halls, gymnasiums, and libraries. g. Warehouse that are conditioned spaces, including storage and distribution building s, refrigerated warehouses, and storage rental facilities. h. All other buildings, including any building use not covered in the eight listed building use types above and data centers using Standard 90.4, shall use the energy credits required
and available for the “Other” category.
Table 11.5.1-2 Renewable Adjustment Credits
| Building Use Type | PV by Climate Zone adj | Col3 | Col4 | Col5 | Col6 | Col7 | Col8 | Col9 | Col10 | Col11 | Col12 | Col13 | Col14 | Col15 | Col16 | Col17 | Col18 | Col19 | Col20 | PV, incl W/ft2 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Building Use Type | 0A | 0B | 1A | 1B | 2A | 2B | 3A | 3B | 3C | 4A | 4B | 4C | 5A | 5B | 5C | 6A | 6B | 7 | 8 | 8 |
| Multifamily | 6 | 7 | 8 | 7 | 8 | 18 | 16 | 19 | 20 | 13 | 13 | 14 | 6 | 9 | 13 | 6 | 7 | 6 | 5 | 0.1 |
| Health care | 3 | 3 | 3 | 3 | 3 | 4 | 3 | 4 | 7 | 5 | 7 | 3 | 2 | 3 | 3 | 3 | 3 | 2 | 2 | 0.1 |
| Hotel/motel | 4 | 8 | 9 | 9 | 9 | 12 | 10 | 13 | 8 | 9 | 10 | 8 | 8 | 12 | 9 | 9 | 10 | 8 | 5 | 0.1 |
| Office | 6 | 6 | 7 | 7 | 12 | 8 | 8 | 9 | 10 | 7 | 9 | 7 | 6 | 8 | 7 | 6 | 7 | 6 | 5 | 0.1 |
| Restaurant | 1 | 1 | 1 | 1 | 1 | 2 | 1 | 2 | 2 | 1 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 0.1 |
| Retail | 5 | 5 | 6 | 6 | 7 | 8 | 14 | 17 | 16 | 7 | 14 | 12 | 10 | 14 | 12 | 10 | 12 | 10 | 7 | 0.1 |
| Education | 5 | 6 | 7 | 6 | 7 | 9 | 16 | 14 | 12 | 11 | 11 | 9 | 11 | 11 | 9 | 12 | 10 | 12 | 10 | 0.1 |
| Warehouse | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 19 | 20 | 20 | 14 | 20 | 20 | 12 | 17 | 12 | 10 | 0.1 |
| Other | 6 | 6 | 7 | 7 | 7 | 8 | 7 | 9 | 9 | 7 | 9 | 7 | 5 | 8 | 7 | 6 | 7 | 5 | 4 | 0.1 |
EC adj = EC req - PV adj 1 - -------------------------------------------------- Gfloor RAPV netincl 0.20 -
(11.5.1)
where EC adj = adjusted energy credit requirement used instead of the energy credit requirement from Table 11.5.1-1 EC req = energy credit requirement from Table 11.5.1-1 PV adj = PV adj for building type from Table 11.5.1-2 RA net = horizontal projection of roof area available for renewable energy resources not covered by any
ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 183