Table 12.5.1 Modeling Requirements for Calculating Design Energy Cost and Energy Cost Budget (Continued)

14. Modeling Exceptions (continued)Col2
**Exception:**Components and_systems_ in the_proposed design_ may be
excluded from the simulation model provided that
1.
component_energy_ use does not affect the_energy_ use of_systems_
and components that are being considered for trade-off and
2.
the applicable prescriptive requirements of Sections 5.5, 6.5, 7.5,
and 9.5 applying to the excluded components are met.
15. On-Site Renewable Energy
On-site renewable energy_in the_proposed design shall be determined as
follows:
a.
Where a complete_system_ providing_on-site renewable energy_ exists, the
model shall reflect the actual_ system_ type using actual component capaci-
ties and efficiencies.
b.
Where a_system_ providing_on-site renewable energy_has been designed,
the_system_ model shall be consistent with design documents.
c.
Where no_system_ exists or is specified to provide_on-site renewable_
energy, no_system_ shall be modeled.
On-site renewable energy_shall be included in the_budget building
design when required by Section 10.5.1, and shall be determined as
follows:
a.
Where a_system_ providing_on-site renewable energy_ has been
modeled in the_proposed design_, the same_system_ shall be
modeled identically in the_budget building design_, except the
rated capacity shall meet the requirements of Section 10.5.1.1.
Where more than one type of_on-site renewable_ energy system
is modeled, the total capacities shall be allocated in the same
proportion as in the_proposed design_.
b.
Where no_system_ exists or is specified to provide_on-site_
renewable energy in the_proposed design_, on-site renewable
energy shall be modeled as an unshaded photovoltaic system
with the following physical characteristics:

Size: Rated capacity per Section 10.5.1.1

Module Type: Crystalline silicon panel with a glass cover,
19.1% nominal efficiency and temperature coefficient of
–0.19%/°F; performance shall be based on a reference tem-
perature of 77°F and irradiance of 317 Btu/ft2·h.

Array Type: Rack-mounted array with installed nominal
operating cell temperature (INOCT) of 103°F

Total system losses (DC output to AC output): 11.3%

Tilt: 0-degrees (mounted horizontally)

Azimuth:180 degrees
If the_on-site renewable energy system_ cannot be modeled in the
simulation program, Section 12.4.5 shall be used.

220 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)