ASHRAE-90.1-2022- - Page 241

Extracted Content

Table A3.1-1 Assembly U-Factors for Above-Grade Concrete Walls and Masonry Walls (Continued)

Framing Type
and Depth
Rated R-Value of
Insulation Alone
Assembly U-Factors
for 8 in. Normal Weight
145 lb/ft3 Solid Concrete Walls
Assembly U-Factors for 8 in.
Medium Weight 115 lb/ft3
Concrete Block Walls: Solid
Grouted
Assembly U-Factors for
8 in. Medium Weight
115 lb/ft3 Concrete Block
Walls: Partially Grouted
(Cores Uninsulated Except
Where Specified)
No FramingR-0U-0.740U-0.580U-0.480
No FramingUngrouted Cores
Filled with
Loose-Fill Insulation
NANAU-0.350

1 in. Metal Clips at 24 in. on Center Horizontally and 16 in. Vertically

1.0 in.R-3.8U-0.210U-0.195U-0.182
1.0 in.R-5.0U-0.184U-0.172U-0.162
1.0 in.R-5.6U-0.174U-0.163U-0.154
1.5 in.R-5.7U-0.160U-0.151U-0.143
1.5 in.R-7.5U-0.138U-0.131U-0.125
1.5 in.R-8.4U-0.129U-0.123U-0.118
2.0 in.R-7.6U-0.129U-0.123U-0.118
2.0 in.R-10.0U-0.110U-0.106U-0.102
2.0 in.R-11.2U-0.103U-0.099U-0.096
2.5 in.R-9.5U-0.109U-0.104U-0.101
2.5 in.R-12.5U-0.092U-0.089U-0.086
2.5 in.R-14.0U-0.086U-0.083U-0.080
3.0 in.R-11.4U-0.094U-0.090U-0.088
3.0 in.R-15.0U-0.078U-0.076U-0.074
3.0 in.R-16.8U-0.073U-0.071U-0.069
3.5 in.R-13.3U-0.082U-0.080U-0.077
3.5 in.R-17.5U-0.069U-0.067U-0.065
3.5 in.R-19.6U-0.064U-0.062U-0.061
4.0 in.R-15.2U-0.073U-0.071U-0.070
4.0 in.R-20.0U-0.061U-0.060U-0.058
4.0 in.R-22.4U-0.057U-0.056U-0.054
5.0 in.R-28.0U-0.046U-0.046U-0.045
6.0 in.R-33.6U-0.039U-0.039U-0.038
7.0 in.R-39.2U-0.034U-0.034U-0.033
8.0 in.R-44.8U-0.030U-0.030U-0.029
9.0 in.R-50.4U-0.027U-0.027U-0.026
10.0 in.R-56.0U-0.024U-0.024U-0.024
11.0 in.R-61.6U-0.022U-0.022U-0.022

Continuous Insulation Uninterrupted by Framing

No framingR-1.0U-0.425U-0.367U-0.324
No framingR-2.0U-0.298U-0.269U-0.245
No framingR-3.0U-0.230U-0.212U-0.197
No framingR-4.0U-0.187U-0.175U-0.164

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 239