Table A4.2.1 Assembly C-Factors forBelow-Grade WallsCol3
Framing Type and DepthRated R-Value of Insulation AloneSpecified C-Factors
(Wall Only, without Soil and Air
Films)
No framingR-0C-1.140

Exterior Insulation, Continuous and Uninterrupted by Framing

No framingR-5.0C-0.170
No framingR-7.5C-0.119
No framingR-10.0C-0.092
No framingR-12.5C-0.075
No framingR-15.0C-0.063
No framingR-17.5C-0.054
No framingR-20.0C-0.048
No framingR-25.0C-0.039
No framingR-30.0C-0.032
No framingR-35.0C-0.028
No framingR-40.0C-0.025
No framingR-45.0C-0.022
No framingR-50.0C-0.020

Continuous Metal Framing at 24 in. on Center Horizontally

3.5 in.R-11.0C-0.182
3.5 in.R-13.0C-0.174
3.5 in.R-15.0C-0.168
5.5 in.R-19.0C-0.125
5.5 in.R-21.0C-0.120

1 in. Metal Clips at 24 in. on Center Horizontally and 16 in. Vertically

1.0 in.R-3.8C-0.233
1.0 in.R-5.0C-0.201
1.0 in.R-5.6C-0.189
1.5 in.R-5.7C-0.173
1.5 in.R-7.5C-0.147
1.5 in.R-8.4C-0.138
2.0 in.R-7.6C-0.138
2.0 in.R-10.0C-0.116
2.0 in.R-11.2C-0.108
2.5 in.R-9.5C-0.114
2.5 in.R-12.5C-0.096
2.5 in.R-14.0C-0.089
3.0 in.R-11.4C-0.098
3.0 in.R-15.0C-0.082
3.0 in.R-16.8C-0.076
3.5 in.R-13.3C-0.085
3.5 in.R-17.5C-0.071
3.5 in.R-19.6C-0.066
4.0 in.R-15.2C-0.076
4.0 in.R-20.0C-0.063
4.0 in.R-22.4C-0.058

254 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)