Table A9.2-1 Effective Insulation/Framing Layer R-Values for Roof and Floor Insulation Installedbetween Metal Framing (4 ft on Center)

Rated R-Value of
Insulation
Correction
Factor
Framing/Cavity
R-Value
0.001.000.00
4.000.973.88
5.000.964.80
8.000.947.52
10.000.929.20
11.000.9110.01
12.000.9010.80
13.000.9011.70
15.000.8813.20
16.000.8713.92
19.000.8616.34
Rated R-Value of
Insulation
Correction
Factor
Framing/Cavity
R-Value
20.000.8517.00
21.000.8417.64
24.000.8219.68
25.000.8120.25
30.000.7923.70
35.000.7626.60
38.000.7428.12
40.000.7329.20
45.000.7131.95
50.000.6934.50
55.000.6736.85

Table A9.2-2 Effective Insulation/Framing Layer R-Values for Wall Insulation Installed Between Steel Framing

Empty Cavity, No Insulation

4 3.5 R-0.91 0.79 0.91

Insulated Cavity

43.5R-115.56.6
43.5R-136.07.2
43.5R-156.47.8
66.0R-197.18.6
66.0R-217.49.0
88.0R-257.89.6

Table A9.4.2-1 R-Values for Cavity Air Spaces [ a]

ComponentAir Space
Thickness,
in.
Climate Zone 1 Effective
Emittance
Col4Col5Col6Climate Zone 2 Effective
Emittance
Col8Col9Col10Climate Zone 3 Effective
Emittance
Col12Col13Col14
ComponentAir Space
Thickness,
in.
0.050.200.500.820.050.200.500.820.050.200.500.82
Roof0.502.51.91.20.92.41.81.20.92.21.71.10.9
Roof0.753.52.41.41.03.22.21.41.02.82.01.30.9
Roof1.505.63.11.71.14.92.91.61.14.22.51.51.0
Roof3.508.03.81.91.27.03.41.71.15.93.01.61.1
Wall0.502.51.81.20.92.51.81.20.92.51.81.20.9
Wall0.752.82.01.30.92.82.01.30.92.82.01.30.9
Wall1.502.51.81.20.92.51.81.20.92.51.81.20.9
Wall3.502.61.91.30.92.61.91.30.92.61.91.30.9

a. Interpolation shall be permitted to be used for effective emittance values and air space thicknesses between those listed. Extrapolation below an effective emittance of 0.05 is not

permitted.

276 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)