Table A9.4.2-2 Emittance Values of Various Surfaces and Effective Emittances of Air Spaces

SurfaceAverage
Emissivity e
Effective Emissivity of Air SpaceCol4
SurfaceAverage
Emissivity****e
One Surface****e; Other, 0.9Both Surfaces Emissivity****e
Aluminum foil, bright0.050.050.03a
Metalized film, testedb0.050.050.03a
Aluminum sheet0.120.120.06
Aluminum coated paper, polished0.200.200.11
Steel, galv., bright0.250.240.14
Aluminum paint0.500.470.32
Building materials: wood, paper, masonry,
nonmetallic paints
0.900.820.82
Regular glass0.840.770.72
a. When referencing Table A9.4.2-1, use an effective_emittance_ of 0.05.
b. Tested_emittance_ in accordance with ASTM C1224 at 0.05 or less.
a. When referencing Table A9.4.2-1, use an effective_emittance_ of 0.05.
b. Tested_emittance_ in accordance with ASTM C1224 at 0.05 or less.
a. When referencing Table A9.4.2-1, use an effective_emittance_ of 0.05.
b. Tested_emittance_ in accordance with ASTM C1224 at 0.05 or less.
a. When referencing Table A9.4.2-1, use an effective_emittance_ of 0.05.
b. Tested_emittance_ in accordance with ASTM C1224 at 0.05 or less.

Table A9.4.3 Effective R-Values for Fiberglass

Insulation R-Value at Standard Thickness

Rated R-ValueCol23830222119151311
Standard Thickness, in.Standard Thickness, in.129.56.55.563.53.53.5
Nominal Lumber Size, in.Actual Depth of
Cavity, in.
Effective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined Cavity
2  1211.2537
2  109.253230
2 87.252726222119
2 65.521202118
2  43.51413151311
2  42.59.8
2  41.56.36

278 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)