Table G3.1 Modeling Requirements for Calculating Proposed Building Performance and Baseline Building Performance (Continued)

Proposed Building PerformanceBaseline Building Performance
5. Building Envelope (continued)
6. Manual fenestration shading devices, such as blinds or shades, shall be modeled or not modeled the same as in the baseline building design. Automatically controlled fenestra- tion shades or blinds shall be modeled. Permanent shading devices, such as fins, overhangs, and light shelves shall be modeled. 7. Automatically controlled dynamic glazing may be modeled. Manually controlled dynamic glazing shall use the average of the minimum and maximum SHGC and VT. 8. The above-grade wall surface shall be modeled using the ini- tial solar reflectance and thermal emittance determined in accordance with the test methods identified in Section 5.5.3.2.2(a). Where initial test data are unavailable, the wall surface may be modeled with a solar reflectance of 0.25 and a thermal emittance of 0.90. b. To simulate air leakage, infiltration shall be modeled using the same methodology and adjustments for weather and building operation in both the proposed design and the baseline building design. These adjustments shall be made for each simulation time step and must account for but not be limited to weather conditions and HVAC system operation, including strategies that are intended to positively pressurize the building. The air leakage rate of the building envelope shall be converted to appropriate units for the simulation program using one of the methods in Section G3.2.1.7. 1. When whole-building pressurization testing is required or specified during design, and completed in accordance with Section 5.4.3.1.4, the measured air leakage rate of the build- ing envelope (I75Pa) at a fixed building pressure differential of 75 Pa (0.30 in. of water) shall be modeled for purposes of demonstrating compliance with this standard. Informative Note: Before the start of pressurization testing, the maximum air leakage rate of the building envelope (I75Pa) specified in Section 5.4.3.1.4 or as specified in design documents may be simulated to estimate the energy impact of building envelope air leakage. The final measured value is used for compliance; therefore, care should be taken when using estimated air leakage as a trade-off for performance- based code compliance. 2. For buildings providing verification in accordance with Sec- tion 5.9.1.2, the air leakage rate of the building envelope (I75Pa) at a fixed building pressure differential of 75 Pa (0.30 in. of water) shall be 0.45 cfm/ft2.
• Roofs with insulation entirely above deck (A2.2). • Above-grade walls—steel-framed (A3.3). • Below-grade walls—concrete block (A4). • Floors—steel-joist (A5.3). • Slab-on-grade floors shall match the F-factor for unheated slabs from the same tables (A6). • Opaque door types shall be of the same type of construction as the proposed design and conform to the U-factor require- ments from the same tables (A7). e. Vertical Fenestration Areas. For building area types included in Table G3.1.1-1, vertical fenestration areas for new buildings and additions shall equal the percentage in Table G3.1.1-1 multiplied by the gross area of above-grade walls that are part of the exte- rior building envelope and semiexterior building envelope. Where a building has multiple building area types, each type shall use the values in the table. For building areas not shown in Table G3.1.1-1, vertical fenestration areas for new buildings and additions shall equal that in the proposed design or 40% of gross area of above-grade walls that are part of the exterior building envelope and semiexterior building envelope, whichever is smaller, and shall be distributed on each face of the building in the same proportions in the proposed design. The vertical fenestration shall be distributed on each face of the building in the same proportion as in the proposed design. If this would cause the combined vertical fenestration and opaque door area on a given face to exceed the gross above-grade wall area on that face, then the vertical fenestration area on other faces shall be increased in proportion to the gross above-grade wall area of these faces such that the total baseline building vertical fenestration area is equal to that calculated following Table G3.1.1-1. The fenestration area for an existing building shall equal the existing fenestration area prior to the proposed work and shall be distributed on each face of the building in the same proportions as the existing building. f. Vertical Fenestration Assemblies. Fenestration for new build- ings, existing buildings, and additions shall comply with the fol- lowing: • Fenestration U-factors shall match the appropriate require- ments in Tables G3.4-1 through G3.4-8 for the applicable glazing percentage for Uall. • Fenestration SHGCs shall match the appropriate requirements in Tables G3.4-1 through G3.4-8 using the value for SHGCall for the applicable vertical glazing percentage. • All vertical fenestration shall be assumed to be flush with the exterior wall, and no shading projections shall be modeled. • Manual window shading devices such as blinds or shades are not required to be modeled. • Automatic fenestration shading devices shall not be modeled. g. Skylights and Glazed Smoke Vents. Skylight area shall be equal to that in the proposed design or 3%, whichever is smaller. If the skylight area of the proposed design is greater than 3%, baseline skylight area shall be decreased by an identical percentage in all roof components in which skylights are located to reach 3%. Sky- light orientation and tilt shall be the same as in the proposed design. Skylight U-factor and SHGC properties shall match the appropriate requirements in Tables G3.4-1 through G3.4-8 using the value and the applicable skylight percentage. h. Roof Solar Reflectance and Thermal Emittance. The exterior roof surfaces shall be modeled using a solar reflectance of 0.30 and a thermal emittance of 0.90. i. The air leakage rate of the building envelope (I75Pa) at a fixed building pressure differential of 0.3 in. of water shall be 1.0 cfm/ft2. j. Wall Solar Reflectance and Thermal Emittance. Above-grade wall surfaces shall be modeled with a solar reflectance of 0.25 and a thermal emittance of 0.90.

308 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)