Table G3.2.2.5 Climate Conditions under which Economizers are Included forComfort Cooling for Baseline Systems 3 through 8 and 11, 12, and 13

Note: NR means that there is no conditioned building floor area for which economizers are included for the type of zone and climate.

Table G3.2.2.6 Economizer High-Limit Shutoff Temperature

Table G3.2.2.8 Baseline Fan Brake Horsepower

Baseline Fan Motor Brake Horsepower

Notes:

  1. Where A is calculated according to Section 6.5.3.1.1 using the pressure-drop adjustment from the proposed design and the design flow rate of the baseline building system .
  2. Do not include pressure-drop adjustments for evaporative coolers or heat recovery devices that are not required in the baseline building system by Section G3.2.2.9.

Table G3.2.3.7 Type and Number of Chillers

Peak Coincident Cooling Load of
Baseline HVAC Systems Using
Chilled Water
Number and Type of Chillers
300 tons1 liquid-cooled screw chiller
>300 tons, <600 tons2 liquid-cooled screw chillers sized equally
600 tons2 liquid-cooled centrifugal chillers minimum with chillers added so that no chiller is larger than
800 tons, all sized equally

324 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)