ASHRAE-90.1-2022- - Page 327

Extracted Content

Table G3.2.3.11 Heat-Rejection Leaving Water Temperature

Climate ZoneLeaving Water Temperature
5B, 5C, 6B, 865°F
0B, 1B, 2B, 3B, 3C, 4B, 4C, 5A, 6A, 770°F
3A,4A75°F
0A, 1A, 2A80°F

Table G3.2.3.15 Part-Load Performance for VAV Fan Systems

Method 1—Part-Load Fan Power Data

Fan Part-Load RatioFraction of Full-Load Power
0.000.00
0.100.03
0.200.07
0.300.13
0.400.21
0.500.30
0.600.41
0.700.54
0.800.68
0.900.83
1.001.00

Method 2—Part-Load Fan Power Equation

Pfan = 0.0013 + 0.1470  PLR fan + 0.9506  (PLR fan ) [2] - 0.0998  (PLR fan ) [3]

where Pfan = fraction of full-load fan power and PLR fan = fan part-load ratio (current cfm/design cfm)

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 325