Table G3.4-9 Heated Space CriteriaCol2
Climate ZoneHeating Output, Btu/h·ft2
0, 1, 2>5
3>10
4, 5>15
6,7>20
8>25

Table G3.5.1 Performance Rating Method Air Conditioners (efficiency ratings excluding supply fan power)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
EfficiencyTest Procedure
Air conditioners,
air-cooled
<65,000 Btu/hAllSingle-package3.0_COPnfcooling_AHRI 210/240
Air conditioners,
air-cooled
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
Split-system and
single-package
3.5_COPnfcooling_AHRI 340/360
Air conditioners,
air-cooled
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
3.4_COPnfcooling_3.4_COPnfcooling_
Air conditioners,
air-cooled
240,000 Btu/h and
<760,000 Btu/h
240,000 Btu/h and
<760,000 Btu/h
240,000 Btu/h and
<760,000 Btu/h
3.5_COPnfcooling_3.5_COPnfcooling_
Air conditioners,
air-cooled
760,000 Btu/h760,000 Btu/h760,000 Btu/h3.6_COPnfcooling_3.6_COPnfcooling_

Table G3.5.2 Performance Rating Method Electrically Operated Unitary and Applied Heat Pumps—Minimum Efficiency Requirements (efficiency ratings excluding supply fan power)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
Air-cooled
(cooling mode)
<65,000 Btu/hAllSingle package3.0_COPnfcooling_AHRI 210/240
Air-cooled
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
Split-system and
single-package
3.4_COPnfcooling_AHRI 340/360
Air-cooled
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
3.2_COPnfcooling_3.2_COPnfcooling_
Air-cooled
(cooling mode)
240,000 Btu/h240,000 Btu/h240,000 Btu/h3.1_COPnfcooling_3.1_COPnfcooling_
Air-cooled
(heating mode)
<65,000 Btu/h
(cooling capacity)
Single-package3.4_COPnfheating_AHRI 210/240
Air-cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
47°F db/43°F wb
outdoor air
3.4_COPnfheating_AHRI 340/360
Air-cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.3_COPnfheating_2.3_COPnfheating_
Air-cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
47°F db/43°F wb
outdoor air
3.4_COPnfheating_3.4_COPnfheating_
Air-cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.1_COPnfheating_2.1_COPnfheating_

334 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)