Table G3.7-1 Performance Rating Method Lighting Power Density Allowances and Occupancy Sensor Reductions Using the Space-by-Space Method
Lighting Power
Common Space Types [a]
Atrium
Density,
W/ft [2]
<20 ft in height 0.0375 per foot in total height
20 ft and 40 ft in height
Occupancy Sensor
Reduction [b]
10%
10%
40 ft in height 0.50 + 0.025 per foot in total height
Audience Seating Area
Auditorium 0.90 10%
Convention center 0.70 10%
Gymnasium 0.40 10%
Motion picture theater 1.20 10%
Performing arts theater 2.60 10%
In a sports arena 0.40 10%
All other audience seating area 0.90 10%
Banking Activity Area 1.50 10%
Classroom/Lecture Hall/Training Room
Preschool through 12th grade, laboratory, and shop classrooms 1.40 30%
All other classroom/lecture hall/training room 1.40 None
Computer Room 2.14 35%
Conference/Meeting/Multipurpose Room 1.30 None
Copy/Print Room 0.90 10%
Corridor 0.50 25%
Courtroom 1.90 10%
Dining Area
Bar/lounge or leisure dining 1.40 35%
Cafeteria or fast food dining 0.90 35%
Family dining 2.10 35%
All other dining area 0.90 35%
Electrical/Mechanical Room 1.50 30%
Emergency Vehicle Garage 0.80 10%
Equipment Room 1.20 10%
Food Preparation Area 1.20 30%
Guest Room 1.14 45%
Laboratory
Preschool through 12th grade, laboratory, and shop classrooms 1.40 30%
All other laboratory except in or as a classroom 1.40 10%
a. In cases where both a common space type and a building -specific space type are listed, the building -specific space type shall apply. b. For manual -ON or partial-auto-ON occupancy sensors, the occupancy sensor reduction factor shall be multiplied by 1.25. c. For occupancy sensors controlling individual workstation lighting, occupancy sensor reduction factor shall be 30%.
ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 337