Table G3.7-2 Performance Rating Method Lighting Power Density Allowances andOccupancy Sensor Reductions Using the Space-by-Space Method

Lighting Power

Occupancy Sensor

Reduction [b]

Building-Specific Space Types [a]

Casino—Gaming Area

Density,

W/ft [2]

Betting/sportsbook/keno/bingo area 1.34 0%

High-limit game area 2.78 0%

Slot machine/digital gaming area 0.90 0%

Table games area 1.80 0%

Convention Center—Exhibit Space 1.30 35%

Correctional Facilities

Audience seating area 0.70 10%

Classroom 1.30 None

Confinement cells 0.90 10%

Dining area 1.30 35%

Dormitory—Living Quarters 1.11 10%

Facility for the Visually Impaired

Chapel (used primarily by residents) 2.77 10%

Corridor (used primarily by residents) 1.15 25%

Dining (used primarily by residents) 3.32 35%

Lobby (used primarily by residents) 2.26 25%

Recreation room (used primarily by residents) 3.02 10%

Restroom (used primarily by residents) 1.52 45%

Fire Station—Sleeping Quarters 0.30 10%

Gymnasium/Fitness Center

Exercise area 0.90 35%

Playing area 1.40 35%

Health Care Facility

Control room (MRI/CT/Radiology/PET) 2.14 10%

Exam/treatment room 1.50 10%

Hospital corridor 1.00 25%

Lounge 0.80 None

Medical supply room 1.40 45%

Nursery 0.60 10%

Nurse’s station 1.00 10%

Operating room 2.20 10%

Patient room 0.70 10%

a. In cases where both a common space type and a building -specific space type are listed, the building -specific space type shall apply. b. For manual -ON or partial-auto-ON occupancy sensors, the occupancy sensor reduction factor shall be multiplied by 1.25. c. For occupancy sensors controlling individual workstation lighting, occupancy sensor reduction factor shall be 30%.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 339