ASHRAE-90.1-2022- - Page 342
Extracted Content
Table G3.7-2 Performance Rating Method Lighting Power Density Allowances and Occupancy Sensor Reductions Using the Space-by-Space Method (Continued)
Lighting Power
Occupancy Sensor
Reduction [b]
Building-Specific Space Types [a]
Density,
W/ft [2]
Physical therapy room 0.90 10%
Recovery room 0.80 10%
Telemedicine 2.21 10%
Library
Reading area 1.20 15%
Stacks 1.70 15%
Manufacturing Facility
Detailed manufacturing area 2.10 10%
Low bay area (<25 ft floor-to-ceiling height) 1.20 10%
High bay area (25 to 50 ft floor-to-ceiling height) 1.70 10%
Extra-high bay area (>50 ft floor-to-ceiling height) 1.32 10%
Museum
General exhibition area 1.00 10%
Restoration room 1.70 10%
Performing Arts Theater—Dressing Room 0.64 0%
Post Office—Sorting Area 1.20 10%
Religious Facility
Audience seating area 1.70 10%
Fellowship hall 0.90 10%
Worship/pulpit/choir area 2.40 10%
Retail Facilities
Dressing/fitting room 0.89 10%
Hair care 1.04 10%
Manicure/pedicure 0.70 10%
Mall concourse 1.70 10%
Massage 0.81 10%
Sports Arena—Playing Area
Class I facility 4.61 10%
Class II facility 3.01 10%
Class III facility 2.26 10%
Class IV facility 1.50 10%
Natatorium
Class I facility 3.57 0%
a. In cases where both a common space type and a building -specific space type are listed, the building -specific space type shall apply. b. For manual -ON or partial-auto-ON occupancy sensors, the occupancy sensor reduction factor shall be multiplied by 1.25. c. For occupancy sensors controlling individual workstation lighting, occupancy sensor reduction factor shall be 30%.
340 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)