Table H-3 Standard 90.1 Items to Verify (Continued)
| Subsection | Subsection Title | Standard 90.1 Items to Verify for Proper Operation or Inclusion | Status |
|---|---|---|---|
| 6.5.1.1 | Air Economizers | Outdoor air and return air damper control sequence properly configured. High- limit shutoff set properly. Damper leakage and relief air appropriate. Sensor accuracy and calibration. | |
| 6.5.1.2 | Fluid Economizers | Maximum pressure drop (precooling coils, water-to-water heat exchanger). Economizer control integration sequence with heating,mechanical cooling, and inside humidity. | |
| 6.5.2.1 | Zone Controls | Zone box minimum position and operating sequence,deadband, and_set points_ configured properly. | |
| 6.5.2.2 | Hydronic System Controls | Two-pipe changeover control_dead band_ and hydronic heat-pump_system_ controls configured properly. | |
| 6.5.2.3/ 6.5.2.4 | Dehumidification/ Humidification | Humidistatic controls configured properly if applicable. | |
| 6.5.2.5 | Preheat Coils | Control sequence configured properly. | |
| 6.5.3.1 | Fan System Power and Efficiency | Fans are within power limits or meet_efficiency_ requirements. | |
| 6.5.3.2 | Fan Control | Fans are equipped with variable-speed drives or multispeed control where required, and control sensors and sequence are properly implemented.VAV static pressure_set point_ is_reset._ | |
| 6.5.3.3 | Multiple-Zone VAV System Ventilation Optimization Control | Proper configuration of ventilation optimization controls for_VAV systems_. | |
| 6.5.3.4 | Parallel-Flow Fan-Powered VAV Air-Terminal Control | Check for proper sequence control. | |
| 6.5.3.5 | Supply Air Temperature Reset Controls | Proper operation of supply air_reset_ controls for multiple zone systems. | |
| 6.5.3.6 | Fractional Horsepower Fan Motors | For smaller fans, ECM or equivalent_efficiency_ motors have speed control. | |
| 6.5.4.1 | Boiler Turndown | Boiler turndown capability and plant load controls for multiple_boilers_ or modulating burner operation. | |
| 6.5.4.2 | Hydronic Variable Flow Systems | Hydronic systems are variable flow and equipped with_pump_ speed controls where required. | |
| 6.5.4.3 | Chiller and Boiler Isolation | Offline chillers and_boilers_ are properly isolated and_automatic_ controls function as required. | |
| 6.5.4.4 | Chilled- and Hot-Water Temperature Reset Controls | Hydronic temperature_reset_ controls are configured properly where required. | |
| 6.5.6 | Energy Recovery | Energy recovery systems implemented where required for exhaust air_energy_ recovery and service hot-water heat recovery. | |
| 6.5.7 | Exhaust Systems | Proper operation of kitchen and laboratory exhaust air systems where required for demand ventilation including integration of makeup-air units with performance testing at multiple flow rates. | |
| 6.5.8 | Radiant Heating Systems | Radiant heating system controls operate properly and are coordinated with other zone controls. | |
| 6.5.10 | Door Switches | Door switches provide proper control integration. | |
| 6.5.11 | Refrigeration Systems | Refrigeration control elements are properly configured. |