ASHRAE-90.1-2022- - Page 360

Extracted Content

PRE = PBP nre - PBP pre

Replace values in Table 4.2.1.1 with the values from Table I3-1 (deleted values not shown):

Table 4.2.1.1 Building Performance Factors (BPF), Site Energy

Building Area TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Area Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily0.720.710.750.730.760.760.770.750.700.610.710.640.560.630.630.540.570.540.56
Healthcare/hospital0.670.660.680.650.650.610.620.640.630.620.630.610.650.630.680.640.680.690.71
Hotel/motel0.690.690.720.680.690.680.690.700.710.650.690.680.630.660.670.600.640.590.58
Office0.540.540.530.520.520.520.500.540.470.470.520.480.490.520.490.480.500.430.46
Restaurant0.640.610.600.590.600.570.610.620.610.660.650.660.690.690.680.710.710.720.74
Retail0.510.490.480.480.440.430.430.440.440.470.450.500.520.470.520.520.500.480.49
School0.520.570.570.560.520.530.530.520.550.420.490.530.440.500.510.430.420.420.44
Warehouse0.260.260.220.250.210.220.250.210.180.380.270.310.460.370.310.490.420.430.47
All others0.630.620.650.610.560.530.550.550.590.550.550.580.570.570.610.570.570.560.58

Modify Section G1.2.2 as follows:

Modify Section G1.3.2(a) and G1.3.2(p) as follows:

[ … ]

The following documentation shall be submitted to the rating authority :

358 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)