ASHRAE-90.1-2022- - Page 363

Extracted Content

Table J-3 Chiller Performance Curves References

Chiller
Condenser
Type
Output
Variable a
Curve
Type b
X cY cMinimum/
Maximum
Value for
X (I-P °F)
Minimum/
Maximum
Value for
Y (I-P °F)
Rated Values
for X/Y
(I-P °F)
AirEIR-f-TT1CHWTOAT39/6055/12644/95
AirCAP-f-TT1CHWTOAT39/6055/12644/95
AirEIR-f-PLRT3PLR0/11
Water
Water
EIR-f-T
CAP-f-T
T1
T1
CHWT
CHWT
ECT
ECT
39/60
39/60
55/104
55/104
44/85
44/85
WaterEIR-f-PLRT2PLR0/11

a. EIR-f-T is the energy input ratio modifier as a function of temperatures; CAP-f-T is the capacity modifier as a function of temperatures; and EIR-f-PLR

is the energy input ratio modifier as a function of the chiller’s part load ratio. b. T1: Output = Coeff1 + Coeff2 × X + Coeff3 × X [2] + Coeff4 × Y + Coeff5 × Y [2] + Coeff6 × X × Y

T2 : Output = Coeff1 + Coeff2 × X + Coeff3 × X [2]

T3: Output = Coeff1 + Coeff2 × X + Coeff3 × X [2] + Coeff4 × X [3]

c. CHWT : chilled-water temperature

OAT: outdoor-air dry-bulb temperature ECT: entering condenser temperature PLR: part-load ratio = load at a given simulation time step/available capacity at given simulation time step

Table J-4 Chiller Performance Curves for Section 12 (Simulation Input Required in I-P units)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
AAir-cooled <150 tons,
10.100 FL, 13.700
IPLV.IP Path A
EIR-f-T1.777758–0.0382580.000431–0.0053680.000118–0.000115
AAir-cooled <150 tons,
10.100 FL, 13.700
IPLV.IP Path A
CAP-f-T–1.3476970.070674–0.0005660.016793–0.000104–0.000076
AAir-cooled <150 tons,
10.100 FL, 13.700
IPLV.IP Path A
EIR-f-PLR0.0877890.1856961.561411–0.832304
BAir-cooled ≥150 tons,
10.100 FL, 14.00
IPLV.IP Path A
EIR-f-T1.872341–0.0418860.000442–0.0067100.000123–0.000086
BAir-cooled ≥150 tons,
10.100 FL, 14.00
IPLV.IP Path A
CAP-f-T–1.1535350.075066–0.0006220.009777–0.000071–0.000057
BAir-cooled ≥150 tons,
10.100 FL, 14.00
IPLV.IP Path A
EIR-f-PLR0.1180810.1074771.570838–0.794051
CLiquid-cooled positive
displacement <75 tons
0.750 FL, 0.600
IPLV.IP Path A
EIR-f-T2.001725–0.0449570.000484–0.0082960.000168–0.000125
CLiquid-cooled positive
displacement <75 tons
0.750 FL, 0.600
IPLV.IP Path A
CAP-f-T–0.9075980.073300–0.0006530.003700–0.0000540.000006
CLiquid-cooled positive
displacement <75 tons
0.750 FL, 0.600
IPLV.IP Path A
EIR-f-PLR0.2437300.1659720.586099
DLiquid-cooled positive
displacement ≥75 and
<150 tons 0.720 FL,
0.560_IPLV_.IP Path A
EIR-f-T1.679306–0.0419600.000456–0.0020810.000128–0.000125
DLiquid-cooled positive
displacement ≥75 and
<150 tons 0.720 FL,
0.560_IPLV_.IP Path A
CAP-f-T–0.8577910.074596–0.0006700.001523–0.0000420.000012
DLiquid-cooled positive
displacement ≥75 and
<150 tons 0.720 FL,
0.560_IPLV_.IP Path A
EIR-f-PLR0.2089820.2240010.561479
ELiquid-cooled positive
displacement ≥150 and
<300 tons 0.660 FL,
0.540_IPLV_.IP Path A
EIR-f-T1.136125–0.0346080.0004010.0080060.000058–0.000131
ELiquid-cooled positive
displacement ≥150 and
<300 tons 0.660 FL,
0.540_IPLV_.IP Path A
CAP-f-T–0.4249420.047087–0.0004580.006232–0.0000700.000058
ELiquid-cooled positive
displacement ≥150 and
<300 tons 0.660 FL,
0.540_IPLV_.IP Path A
EIR-f-PLR0.2466440.1845760.566463
FLiquid-cooled positive
displacement ≥300 and
<600 tons 0.610 FL,
0.520_IPLV_.IP Path A
EIR-f-T1.161349–0.0405570.0004310.0135670.000003–0.000103
FLiquid-cooled positive
displacement ≥300 and
<600 tons 0.610 FL,
0.520_IPLV_.IP Path A
CAP-f-T0.0127660.033086–0.0003500.004004–0.0000610.000083
FLiquid-cooled positive
displacement ≥300 and
<600 tons 0.610 FL,
0.520_IPLV_.IP Path A
EIR-f-PLR0.2449260.2188900.532972
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
EIR-f-T0.874461–0.0413900.0004300.022262–0.000058–0.000097
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
CAP-f-T0.1223040.024081–0.0002930.006302–0.0000810.000116
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
EIR-f-PLR0.2643710.2633020.471690

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 361