ASHRAE-90.1-2022- - Page 364

Extracted Content

Table J-4 Chiller Performance Curves for Section 12 (Simulation Input Required in I-P units) (Continued)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
HLiquid-cooled
centrifugal <150 tons
0.610 FL, 0.550
IPLV.IP Path A
EIR-f-T0.474969–0.0360870.0002230.030749–0.0001780.000094
HLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.610 FL,
0.550_IPLV_.IP Path A
CAP-f-T–0.4540520.056252–0.0006690.000736–0.0000990.000249
HLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.610 FL,
0.550_IPLV_.IP Path A
EIR-f-PLR0.3042060.0738660.621457
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
EIR-f-T0.596868–0.0227680.0001310.023536–0.0001300.000024
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
CAP-f-T0.9470090.032913–0.000354–0.0201510.0000620.000148
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
EIR-f-PLR0.2769610.1017490.621383
JLiquid-cooled
centrifugal ≥400 tons
<600 tons 0.560 FL,
0.500_IPLV_.IP Path A
EIR-f-T0.551957–0.0361960.0003000.028396–0.0001470.000029
JLiquid-cooled
centrifugal ≥600 tons
0.560 FL, 0.500
IPLV.IP Path A
CAP-f-T–0.7022420.077132–0.000785–0.005637–0.0000330.000145
JLiquid-cooled
centrifugal ≥600 tons
0.560 FL, 0.500
IPLV.IP Path A
EIR-f-PLR0.2908910.0593660.649421
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
EIR-f-T2.054048–0.0424060.000450–0.0098130.000140–0.000093
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
CAP-f-T–1.3256520.074160–0.0006070.013871–0.000088–0.000069
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
EIR-f-PLR0.0368490.1007921.614142–0.748013
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
EIR-f-T1.673814–0.0411780.000429–0.0034240.000109–0.000084
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
CAP-f-T–0.9393450.074488–0.0006150.005127–0.000048–0.000048
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
EIR-f-PLR0.0957110.0099031.543396–0.646737
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
EIR-f-T2.018167–0.0451110.000485–0.0085030.000168–0.000124
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
CAP-f-T–0.9137520.073361–0.0006540.003787–0.0000540.000006
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
EIR-f-PLR0.1072000.1826110.705182
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
EIR-f-T1.849951–0.0434090.000467–0.0051870.000146–0.000123
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
CAP-f-T–0.8403420.071938–0.0006410.002703–0.0000470.000007
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
EIR-f-PLR0.183811–0.0444170.855660
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
EIR-f-T1.020192–0.0300460.0003630.0085040.000053–0.000135
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
CAP-f-T–0.4517490.051393–0.0004900.004351–0.0000580.000050
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
EIR-f-PLR0.0909360.2078120.696735
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
EIR-f-T1.189071–0.0385850.0004150.0115740.000017–0.000108
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
CAP-f-T–0.0638520.038321–0.0003880.002935–0.0000540.000072
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
EIR-f-PLR0.1036650.1480240.744887
QLiquid-cooled positive
displacement ≥600
tons 0.585 FL, 0.380
IPLV.IP Path B
EIR-f-T0.916144–0.0415410.0004360.020987–0.000047–0.000100
QLiquid-cooled positive
displacement ≥600
tons 0.585 FL, 0.380
IPLV.IP Path B
CAP-f-T0.1318800.023312–0.0002860.006699–0.0000840.000116
QLiquid-cooled positive
displacement ≥600
tons 0.585 FL, 0.380
IPLV.IP Path B
EIR-f-PLR0.0617060.2617110.677017

362 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)